Kohler 40COZ/33CFOZ Service Manual page 85

Marine generator set
Table of Contents

Advertisement

1
1. Ohmmeter connections across AC leads
Figure 7-16 Exciter Armature Continuity Check
7. Using a megohmmeter, apply 500 volts DC to the
rotor shaft and either AC lead. See Figure 7-17.
Follow the instructions of the megohmmeter
manufacturer when performing this test. A reading
of approximately 5--7 kOhms and higher indicates
the field winding is functional. A reading of less than
5--7 kOhms
(approximately)
deterioration of the winding insulation and possible
current flow to ground.
TP-5737 5/01
9
R12758-8
TP-5353-7
indicates
8. Repair or replace the rotor.
Repair the AC leads if this test indicates the leads
are shorted to ground. Solder and insulate any
splices used. Use new sleeving when tying the
leads to the shaft or the heat sink.
Replace the rotor assembly if this test shows the
armature is shorted to ground.
3-100
1. Megohmmeter connections across either AC lead and
rotor shaft
Figure 7-17 Exciter Armature High Voltage Test
Section 7 Component Testing and Adjustment
1
M
3-100
R12758-8
TP-5353-7
71