Stator - Kohler 40COZ/33CFOZ Service Manual

Marine generator set
Table of Contents

Advertisement

7.6 Stator

Note: When replacing the rotor or stator, use a
skewed (slanted) rotor with a straight stator
per original manufacturer.
Stator Test Procedure
1. Check the generator output leads for proper
connections. See Section 9, Wiring Diagrams.
2. Check the stator windings for:
a. Shorted windings: Replace the stator if burnt or
hot windings exist. See Figure 7-12.
Note: Disconnect V7, V8, V9, and V0 leads at
the controller AC fuse terminal blocks
before performing the open winding test.
b. Open windings: With an ohmmeter, check each
pair of leads for low resistance readings
(continuity). High resistance across A or low
resistance (continuity) across B and ground
indicates a faulty stator; if so, replace the stator.
See Figure 7-13.
1
A
B
C
Figure 7-13 Stator Winding Test
68
Section 7 Component Testing and Adjustment
4
2
5
3
A.
Continuity/resistance
B.
No continuity
C.
No continuity
2
1. Leads
2. Windings
Figure 7-12 Stator
6
7
10
8
1
11 9
12
TP-5737 5/01
3-100
R12758-8
TP-5353-7