Framing must be accomplished after the Model ZC-80 is set in
place.
The chimney can be installed after framing, but installa-
tion is considerably more difficult and, in some cases,
impossi-
ble.
Therefore, it is recommended that the chimney be installed
prior to framing when a choice exists.
'~ ~t:
LJ
±
lZ
rr~'Bl.lllzm<f1~mm_"
Atlj<lcelll
noom
01
~
~\~
:Jl.
Exlclior Cha:;e
Interior
Locntion
FIGURE 6
Above (Figure 6) are framing location examples with depth dimen-
sions for some typical configurations.
These are finished meas-
urements so install accordingly.
1.
Before framing,
combustible floor coverings (carpet, tiles,
etc.) must be removed to outer dimension of unit framing,
includ-
ing the 16" x 42 1/2" area for the hearth extension.
FIGURE 1·A: Safety shield for millboard hearth
extension.
Attach safety
shield using
sheet metal
screws
WARNING! Install the hearth
protector only as specified.
The hearth extension must
extend a minimum of 16" in
front of the fireplace opening
and must be 42 1/2" wide mini-
mum.
FIGURE 1-B: Safety shields for
brick or rock hearth (Note: Cut
vertical shield to Fit Installation
height as needed.
Use 26 'Ga.
Mini-
mum metal being sure to cover any
combustibles on the base.)
7
o
"'==~~--7'Attach
safety
shield using
sheet metal
scews