Inspection and service

7
Inspection and service
7.1

General notes

NOTICE: System damage due to inadequate cleaning
and maintenance.
▶ Carry out cleaning and maintenance at least once a
year. In the course of this work, check the entire
heating system including the neutralising system for
correct function.
▶ Immediately correct all faults to prevent system
damage.
Annual inspection and service are part of the warranty
terms.
Use only genuine spare parts from the manufacturer.
Spare parts can be ordered from the manufacturer's
spare parts catalogue.
Arrange an annual inspection and responsive maintenance and
inspection contract with the service department of the manufacturer or
with your contractor.
The manufacturer's address can be found on the last page.
7.2

Why is regular maintenance important?

Have your heating system regularly serviced:
• to maintain a high level of efficiency and to operate the system
economically (low fuel consumption),
• to achieve a high level of operational reliability,
• to maintain the cleanest possible combustion
7.3

Checking and correcting the water pressure

The heating system must contain sufficient water to ensure its correct
function.
▶ If the water pressure in the heating system is too low, top up with
water.
▶ Check the water pressure monthly.
7.3.1 When should you check the water pressure in the heating
system?
The fill and top-up water quality must comply with the
specifications in the operator's log supplied.
Air pockets may form in the heating system through the
fill or top-up water releasing gases.
▶ Vent the heating system (e.g. bleeding the radiators).
▶ If required, top up with water.
Recently added fill or top-up water loses much of its volume in the first
few days because it releases gases. With new systems you should
therefore initially check the heating water pressure on a daily basis, and
then at gradually longer intervals.
• Once the heating system is hardly losing any volume, check the
heating water pressure monthly.
8
A distinction is generally made between open vented and sealed
unvented systems. In practice, open vented systems are rarely installed
nowadays. We will therefore be using a sealed unvented heating system
to demonstrate how you can check the water pressure. All settings will
have already been made by the contractor when the system was first
commissioned.

7.3.2 Sealed unvented systems

NOTICE: System damage due to frequent topping up!
Subject to the water quality, your heating system can be
damaged through corrosion or scaling.
▶ Ensure that the heating system is vented correctly.
▶ Check the heating system for leaks and the expansion
vessel for functionality.
▶ Observe the requirements regarding water quality
(see operator's log).
▶ If water loss occurs frequently, locate the cause and
rectify the problem without delay.
NOTICE: System damage due to temperature stresses!
▶ Only fill the heating system when cold (the flow
temperature must not exceed 40 °C).
▶ During operation, only fill the heating system via the
fill valve in the heating system pipework (return).
For sealed unvented systems, the pressure gauge needle [3] must be
within the green band [2]. The red needle [1] of the pressure gauge
must be set to the pressure required for the heating system.
▶ Checking the heating system water pressure.
▶ Top up the heating water if the pressure gauge needle [3] drops below
the green band [2].
▶ Top-up with water via the filling facility.
▶ Vent the heating system.
▶ Check the water pressure once more.
1
Fig. 3 Manometer for sealed unvented heating systems
[1]
Red needle
[2]
Green marking
[3]
Manometer needle

7.3.3 Installations with automatic pressurisation units

For installations in which an automatic pressurisation unit is integrated,
observe the manufacturer's instructions.
The water quality requirements also apply here (see operator's log).