Daikin VAM-FA Technical Data Manual page 82

Heat reclaim ventilation
Table of Contents

Advertisement

15
Control systems
15 - 4 Applicable patterns
15 - 4 - 3 Central control system (DCS302B61)
Collective operation [Adapter PCB for remote control KRP2A Series]
Purposes and functions
1
A maximum of 64 groups can be controlled the operation of "ON /
OFF" collectively. (For the individual control, use the central
15
remote control or the unified On / Off control.)
Cautions
1. Adapter PCB can be installed in any unit connected to the
central transmission line.
2. It cannot be used with other central control.
3. The setting of group number is not required.
4. The HRV unit judges the ventilation mode, individually.
Example control wiring
Connecting line can be
extended up to 150 m
maximum.
B1 B2 BC
PCB board KRP2A series
(installed in the indoor
X18A
P1 P2
Indoor unit
P1 P2
P1 P2
Indoor unit
P1 P2
80
• Heat reclaim ventilation • VAM-FA/FB
Remote control board
(local supply)
ON / OFF
No-voltage normally
open contact for
W1 W2 W3 W4
micro-current
F1 F2
J1 J2
JC
F1 F2
X11A
SS1
X9A
X10A
P1 P2
HRV unit
Remote control
P1 P2
for HRV unit
F1 F2
J1 J2
JC
F1 F2
X11A
SS1
X9A
X10A
P1 P2
HRV unit
• Ventilation • Heat reclaim ventilation
Switch setting of the HRV unit
The initial setting is required by the remote control for the indoor
unit or HRV unit.
• Collective zone interlock setting
......................................"OFF" (as per factory setting)
• The setting of switch on the PCB
• Voltage / no-voltage changeover switch(SS1)
......................................"no-voltage"
*
Remote control mode changeover switch (RS1) should be
selected.
Optional accessories required
Adapter PCB for remote control KRP2A61
(HC0038)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vam-fb

Table of Contents