Daikin VAM-FA Technical Data Manual page 70

Heat reclaim ventilation
Table of Contents

Advertisement

15
Control systems
15 - 3 Basic patterns
15 - 3 - 1 List of control system
Control
Purposes and applications
system
1
• When the HRV unit is interlocked to 2
or more groups of indoor units, The
HRV unit operates if one of indoor unit
15
in the groups is in operation. The HRV
unit can also be operated
independently by remote control for
indoor unit, even if the indoor unit is not
in operation.
[Unified On / Off Controller]
• A maximum of 16 groups can be
controlled of "On / Off" by one controller,
and up to four controllers can be
installed in one system.
[Schedule Timer]
• One schedule timer can control the
weekly schedule of up to 128 units.
[Adapter PCB for remote control]
• One adapter PCB can control up to
64 groups collectively.
• The Central remote controller can
control the zone operation of the
several groups of the units collectively.
• Central remote controller can control
the independent operation of HRV unit
in each zone.
68
• Heat reclaim ventilation • VAM-FA/FB
Indoor unit
Remote controller for indoor unit
Remote control for indoor unit
Indoor unit
Remote control
for indoor unit
Indoor unit
Remote control for indoor unit
Indoor unit
Remote control for indoor unit
Indoor unit
Remote control for indoor unit
• Ventilation • Heat reclaim ventilation
Description of system
Central transmission line
Indoor unit
HRV unit
Remote control for indoor unit
Adapter PCB for remote conrol
Unified On / Off
HRV unit
controller or
Schedule timer
or Adapter PCB
for remote
control
Remote control for HRV unit
HRV unit
HRV unit
Remote control for HRV unit
HRV unit
Optional accessories
required
KRP2A61
♦Adapter PCB for remote
control
(One adapter PCB should
be installed in either the
HRV unit or the indoor
unit.)
DCS301B61
♦Unified On / Off
Controller
(up to 4 controllers)
DST301B61
♦Schedule timer
KRP2A61
♦Adapter PCB for remote
control (not possible to
use together with other
central control)
* One of the above control
should be installed in indoor
unit.
(However, only KRP2A61 can
also be installed in HRV unit.)
DCS302B61
♦Central remote control
Central
remote
control