Heat reclaim ventilation
Table of Contents

Advertisement

15
Control systems
15 - 4 Applicable patterns
15 - 4 - 2 To connect the remote control to the HRV unit
(Part 1) single-group interlocked operation
Purposes and functions
1
When the HRV unit is interlocked to the single-group control
system, the remote control for HRV unit will be connected to
change the setting mode at the HRV unit side.
15
Cautions
1. It is not possible to set the "On / Off" and "timer" setting by
the remote control for HRV unit. Also it is not possible to
display the filter-sign and malfunction code neither on the
remote control for indoor unit nor on the remote control for
HRV unit.
2. Since this is two remote control system (for Indoor unit and
HR unit), the Master / Slave setting is required.
Remote control for
Indoor unit
HRV unit
(Part 2) Centralized control operation
Purposes and functions
• Beside the operation by central remote control, the remote
control for HRV unit can change the ventilation mode setting,
the ventilation air flow setting and etc.
Cautions
1. In case of Zone control, the operation / stop and the timer
setting cannot be done by the remote control for the HRV
unit. (The operation lamp blinks twice to indicate that the
operation is not possible.)
2. The remote control for the HRV unit cannot set the group
no. for centralized control. In this case, the remote control
for the indoor unit has to be connected once for this setting.
3. It is not possible to have Precool / preheat time setting
function.
78
• Heat reclaim ventilation • VAM-FA/FB
Setting
Slave
Master
• Ventilation • Heat reclaim ventilation
Example of control wiring
F1 F2
P1 P2
Indoor unit
P1 P2
Remote control
for indoor unit
Connecting line can be
extended up to 500 m
maximum.
Switch setting of the HRV unit
• No change is required (as per factory setting)
Optional accessories required
• Remote control BRC301B61
Example of control wiring
To central control
F1 F2
P1 P2
Indoor unit
P1 P2
Remote control
for indoor unit
Switch setting of the HRV unit
Group no. setting for central control is required.
It is necessary to set the group number for each unit connected to
the central transmission line (terminal no. (F1) and (F2)).
Initial setting is required by the remote control for indoor unit.
• In case of collective / individual control
Collective zone interlock setting
........................."OFF" (as per factory set)
• In case of zone control
Collective zone interlock setting
........................."ON" [17(27)·8·02]
Optional accessories required
• Remote control BRC301B61
J1 J2
JC
F1 F2
X11A
SS1
X9A
X10A
P1 P2
HRV unit
P1 P2
Remote control
for HRV unit
(HC0033)
J1 J2
JC
F1 F2
X11A
SW
X9A
X10A
P1 P2
HRV unit
P1 P2
Remote control
for HRV unit
(HC0035)