Pump Requirements; Brute Boiler Flow And Head Requirements; Brute Water Heater Flow And; Head Requirements - Bradford White Brute BNTH1000 Installation And Operation Instructions Manual

Hide thumbs Also See for Brute BNTH1000:
Table of Contents

Advertisement

1200
6"
Installations in the U.S. require exhaust vent pipe that is a combination of PVC and
CPVC complying with ANSI/ASTM D1785 F441, polypropylene pipe that complies
Brute
B
TM
RUTE. BOILERS AND VOLUME WATER HEATERS, 1,000 & 1,200 MBTU/h
with ULC S636, or stainless steel complying with UL 1738. Installations in Canada
require exhaust vent pipe that is certified to ULC S636.
NOTE: The first 12" (30cm) of vent must be CPVC if using a PCV vent system.
Section 5
Intake (air) pipe may be ABS, PVC, CPVC or galvanized material.
Closet and alcove installations do not allow the use of PVC under any circumstances

PUMP REQUIREMENTS

*To calculate max equivalent length, measure the linear feet of the pipe, and add 5
feet (1.5m) for each elbow used.
5.1

Brute Boiler Flow and Head Requirements

20°F
Flow
H/L
Size
gpm
feet
1000
95
30
1200
114
37
Intake
11°C
(Air)
Flow
H/L
Size
Pipe
Size
1000
lpm
m
6"
1200
6"
1000
359
9.0
Installations in the U.S. require exhaust vent pipe that is a combination of PVC and
1200
432
11.3
CPVC complying with ANSI/ASTM D1785 F441, polypropylene pipe that complies
with ULC S636, or stainless steel complying with UL 1738. Installations in Canada
Table 7.
Water Flow Requirements
require exhaust vent pipe that is certified to ULC S636.
NOTE: The first 12" (30cm) of vent must be CPVC if using a PVC vent system.
Intake (air) pipe may be ABS, PVC, CPVC or galvanized material.
Closet and alcove installations do not allow the use of PVC under any circumstances
*To calculate max equivalent length, measure the linear feet of the pipe, and add 5
feet (1.5m) for each elbow used.
5.2
Brute Water Heater Flow and Head Requirements
Temperature Rise
20°F
Flow
Size
gpm
1000
95
114
1200
Maximum water hardness of 10 grains per gallon allowed.
Table 8.
Brute Water Heater Flow Data
40°F
Size
gph
1000
2857
1200
3420
22°C
Size
L/h
1000
10799
1200
12927
6"
100 ft
Temperature Rise in °F
25°F
30°F
Flow
H/L
Flow
H/L
gpm
feet
gpm
feet
75
20
62
15
91
26
76
18
Temperature Rise in °C
Exhaust
14°C
17°C
(Vent)
Flow
H/L
Flow
H/L
Pipe
Equivalent Length*
lpm
m
6"
lpm
100 ft
m
6"
100 ft
283
6.0
234
4.5
344
7.9
288
5.5
11°C
H/L
Flow
feet
lpm
30
359
37
430
Design Temperature Rise Across Boiler
50°F
60°F
gph
gph
2286
1905
2736
2280
Design Temperature Rise Across Boiler
28°C
33°C
L/h
L/h
8641
7201
10369
8641
30 m
35°F
Flow
H/L
Flow
gpm
feet
gpm
54
11
48
65
13
57
Maximum
19°C
Allowable
Flow
H/L
Flow
lpm
30 m
m
lpm
30 m
204
3.3
182
246
4.0
216
H/L
m
9.0
10.8
70°F
80°F
90 °F
gph
gph
gph
1633
1429
1270
1954
1710
1520
39°C
44°C
50°C
L/h
L/h
L/h
6173
5402
4801
7407
6482
5761
40°F
45°F
H/L
Flow
H/L
feet
gpm
feet
9
42
7
10
51
8
22°C
25°C
H/L
Flow
H/L
m
lpm
m
2.7
159
2.1
3.0
193
2.4
100°F
120°F
gph
gph
1143
952
1368
1140
56°C
67°C
L/h
L/h
4321
3599
5185
4319
Page 17
140°F
gph
816
977
78°C
L/h
3084
3701