Troubleshooting Tables (All Codes) - Bradford White Brute BNTH1000 Installation And Operation Instructions Manual

Hide thumbs Also See for Brute BNTH1000:
Table of Contents

Advertisement

Page 96
12.3 Troubleshooting Table
This table includes a listing of the faults that might be generated by the controllers, and displayed on the
Touch Screen. Some of these can be corrected by an installer changing a parameter, while other conditions
are more complicated, and will require a service technician.
The first column lists the code number that will appear at the beginning of the Lockout or Hold message in
the orange bar at the bottom of the screen. The second column lists the text as it will appear on the Touch
Screen. The third column shows whether the condition will cause a Hold, or Lockout, or both. The fourth
column lists some suggestions for corrective action.
Code
Description
1
Unconfigured safety data
2
Waiting for safety
data verification
3
Internal fault:
Hardware fault
4
Internal fault:
Safety Relay key feedback error
5
Internal fault:
Unstable power (DC DC) output
6
Internal fault:
Invalid processor clock
7
Internal fault:
Safety relay drive error
8
Internal fault:
Zero crossing not detected
9
Internal fault:
Flame bias out of range
10
Internal fault:
Invalid burner control state
Code
Description
L or H Procedure
L
1. New device, complete device configuration and
safety verification.
2. If fault repeats, replace module
L
1. Device in Configuration mode and safety
parameters need verification and a device
needs reset to complete verification.
2. Configuration ended without verification, re
enter configuration, verify safety
parameters and reset device to complete
verification.
3. If fault repeats, replace module.
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
L
Internal fault
1. Reset module
2. If fault repeats, replace module.
L or H Procedure
B
W
RADFORD
HITE