Adding additional refrigerant
Figure of Simultaneous twin
Outdoor Unit
Formula for calculating the amount of additional refrigerant
(Formula will differ depending on the diameter of the liquid connecting side pipe.)
* 1 to 7 are the lengths of the pipes shown in the figures above (unit: m).
Simultaneous twin
Diameter of connecting pipe
(liquid side)
1
Ø12.7
Ø9.5
Simultaneous triple
Diameter of connecting pipe (liquid side)
1
Ø12.7
Ø9.5
Simultaneous double twin
Diameter of connecting pipe
Outdoor
unit
1
SM2244
Ø12.7
SM2804
Ø12.7
Indoor Unit
Indoor Unit
2
3
1
Indoor Unit
Outdoor Unit
4
Amount of additional
refrigerant per meter
α
2
3
Ø9.5
80
2
3
4
Ø9.5
Ø9.5
(liquid side)
2, 3
4 to 7
Ø9.5
Ø6.4
Ø9.5
Ø9.5
Outdoor Unit
Figure of Simultaneous double twin
Indoor Unit
5
2
1
(g/m)
amount of refrigerant added for branch piping
β
40
Amount of additional
refrigerant per meter
(g/m)
α
β
80
40
Amount of additional
refrigerant per meter (g/m)
α
β
80
40
80
40
16
Figure of Simultaneous triple
Indoor Unit
Indoor Unit
4
2
1
Indoor Unit
Indoor Unit
6
7
3
Amount of additional refrigerant (g) =
Amount of refrigerant added for main pipe +
α × ( 1 – 28) + β × ( 2 + 3 – 4)
Amount of additional refrigerant (g) =
Amount of refrigerant added for main pipe +
amount of refrigerant added for branch
α × ( 1 – 28) + β × ( 2 + 3 + 4 – 6)
Amount of additional refrigerant (g) =
Amount of refrigerant added for main pipe
+ amount of refrigerant added for first
branch piping + amount of refrigerant
γ
added for second branch piping
α × ( 1 – 28) + β × ( 2 + 3 – 4) +
20
γ × ( 4 + 5 + 6 + 7)
α × ( 1 – 28) + β × ( 2 + 3 – 4) +
40
γ × ( 4 + 5 + 6 + 7)
Indoor Unit
3
piping