Panasonic U-72MF2U9 Technical Data Manual page 39

3way vrf system
Hide thumbs Also See for U-72MF2U9:
Table of Contents

Advertisement

3. ELECTRICAL WIRING
3. ELECTRICAL WIRING
CAUTION
(1) When linking outdoor units in a network, see the section "ATTENTION!".
(2) Do not install the inter-unit control wiring in a way that forms a loop.
Outdoor unit
Indoor unit
(3) Do not install inter-unit control wiring such as star branch
wiring. Star branch wiring causes mis-address setting.
Outdoor unit
NO
(4) If branching the inter-unit control wiring, the number of branch points should be 16 or fewer.
Central Controller
Outdoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Outdoor unit
: Branch point
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
Prohibited
Indoor unit
Indoor unit
Indoor unit
Branch point
Indoor unit
Indoor unit
Indoor unit
2 - 23
Design of 3WAY VRF SYSTEM
Design of 3WAY VRF SYSTEM
Prohibited
Indoor unit
Indoor unit
Indoor unit
Indoor unit
1
2
3
4
5
6
7
8
9

Advertisement

Table of Contents
loading

This manual is also suitable for:

U-144mf2u9U-96mf2u9U-120mf2u9

Table of Contents