3. ELECTRICAL WIRING
3. ELECTRICAL WIRING
Wiring sample
Inter-unit control wiring (U1, U2)
Inter-outdoor unit control wiring (1, 2)
Terminal board for power supply
*1
*2
*3
Wiring panel
(Front)
Wiring panel
(Bottom)
*4 ・ Hollow for jigsaw holes (Maximum allowed per hole is ø1-7/8" (ø48).)
・ Be sure to use waterproof conduit for electrical wiring to the outdoor unit.
・ Protective structure is necessary to avoid raindrops through wiring ports.
・ Hollow to cut out openings for wiring ports on the panel with a jigsaw.
Electronic component box
2P terminal board *
1
2P terminal board *
1
3P terminal board *
2
Earth terminal *
3
Tightening torque
lbs.inch
N · m
11
3
1.25
0.25
55
2
6.2
0.2
73
4
8.2
0.4
Fit wires with cable clamps.
Fit power supply and Inter-unit
control wires with cable clamps
respectively (field supply).
Hollow to cut out opening *
Hollow to cut out opening
*
4
ø1-3/4" (ø44) (Power supply wiring inserting port: knockout holes)
ø1-3/8" (ø35) (Power supply wiring inserting port: knockout holes)
ø7/8" (ø23) (Inter-unit control wiring inserting port: knockout holes)
4
ø1-3/8" (ø35) (Power supply wiring inserting port: knockout holes)
ø7/8" (ø23) (Inter-unit control wiring inserting port: knockout holes)
ø1-3/4" (ø44) (Power supply wiring inserting port: knockout holes)
2 - 27
Design of 3WAY VRF SYSTEM
Design of 3WAY VRF SYSTEM
Unit: in. (mm)
1
2
3
4
5
6
7
8
9