1. Outdoor Unit
1-3. Dimensional Data
U-72MF2U9, U-96MF2U9, U-120MF2U9, U-144MF2U9
1
2
3
Installing the Outdoor Unit
(1) Use anchor bolts (15/32" or M12) or similar to securely anchor the unit in place. (Fig. 2)
(2) Make sure the rubber vibration insulator and platform extend to the inside of the legs. In addition, the washers used to anchor
4
the unit from the top must be larger than the installation anchor holes. (Figs. 2 and 3)
Type 120/144
D
5
Vibration insulator
G
D
F
6
<Detailed view of legs>
2 support area per each leg (×2) must install vibration insulator material and mount.
The area of dimension marked with the asterisk (*) must cover the base.
Unit: in. (mm)
View F (area D/E)
Anchor bolt
Washer
7
Vibration insulator
19-32 (15)
*2-51/64 (71)
Base
<Detailed view of installation holes>
8
Unit: in. (mm)
Installation elongated hole
(19/32 (15) × 53/64(21))
9
45-9/32(1,150)
(Installation hole pitch)
Top view
46-29/64(1,180)
Front view
D
Vibration insulator
D
E
D
Leg
Anchor bolt
Leg
Vibration insulator
*3-15/16 (100)
Base
19/32 (15)
Fig. 3
3WAY VRF SYSTEM Unit Specifications
*1. The tubing is routed out from the bottom.
*2. The tubing is routed out from the front.
39-3/8(1,000)
Side view
D
E
H
E
D
View G (area D)
Washer
Vibration insulator
*3-15/16 (100)
4 - 10
unit : in.(mm)
Unit: in. (mm)
E
Vibration insulator
D
Fig. 1
Unit: in. (mm)
View H (area E)
Washer
Anchor bolt
Base
Fig. 2