2.2 SPECIFICATIONS

(1) Indoor units

(a) Ceiling cassette-4way type (FDT)

Model
Item
Power source
Operation data
Nominal capacity
Sound Pressure Level
dB(A)
Exterior dimensions
Height x Width x Depth
Exterior appearance
(Munsell color)
Net weight
Heat exchanger
Air handling equipment
Fan type & Q'ty
Motor <Starting method>
Air flow (Standard)
CMM
External static pressure
Outdoor air intake
Air filter, Q'ty
Shock & vibration absorber
Insulation (noise & heat)
Remote controller
Room temperature control
Safety equipment
Installation data
Refrigerant piping size
Connecting method
Drain pump
Drain
Insulation for piping
IP code
Standard Accessories
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Operation
Cooling
Heating
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) When wireless remote controller is used, fan is 3 speed setting (Hi-Me-Lo) only.
Cooling
kW
mm
kg
W
Pa
wired : RC-EX1A, RC-E5 (option) wireless : RCN-T-36W-E (option)
mm
Outdoor air temperature
DB
WB
DB
27˚C
19˚C
35˚C
20˚C
7˚C
FDT50VF
Panel T-PSA-3BW-E
220-240V~50Hz / 220V~60Hz
5.0
P-Hi : 39 Hi : 33 Me : 31 Lo : 30
Unit 246 × 840 × 840
Panel 35 × 950 × 950
Plaster White
(6.8Y8.9/0.2) near equivalent
UNIT 22 PANEL 5.5
Louver fin & inner grooved tubing
Turbo fan × 1
50 < Direct line start >
P-Hi : 20 Hi : 18 Me : 16 Lo : 14
0
Possible
Pocket plastic net × 1 (Washable)
Rubber sleeve (for fan motor)
Polyurethane form
Thermostat by electronics
Overload protection for fan motor
Frost protection thermostat
Liquid line :φ6.35 (1/4")
Gas line
:φ12.7 (1/2")
Flare piping
Built-in Drain pump
Hose Connectable with VP25
Necessary (both Liquid & Gas lines)
IPXO
Mounting kit, Drain hose
WB
24˚C
6˚C
455
-
-
'12 • PAC-T-174
Adapted to RoHS directive
Heating
5.4
PJF000Z294