Mitsubishi Electric FDT125VNVF Technical Manual page 331

Table of Contents

Advertisement

2) SRK series
Remote controller
Indoor unit display
TIMER
Error code Red LED RUN light
light
Keeps
ON
flashing
5 times
ON
flash
Keeps
2 times
flashing
flash
Keeps
1 time flash
flashing
Keeps
4 times
flashing
flash
Keeps
flashing
ON
1 time flash
7 times
ON
flash
4 times
ON
flash
Keeps
4 times
flashing
flash
7 times
ON
flash
Note (1) * mark in the Description of trouble means that, in ordinary diagnosis, it cannot identify the cause definitely, and, if the trouble is repaired by replacing the part, it
is judged consequently that the replaced part was defective.
(iii) Optional controller in-use
  1) FDT, FDTC, FDEN, FDU, FDUM, FDF series
Indoor unit control PCB
Error code
Red LED
Red LED
Keeps flashing
Stays OFF
Keeps flashing
  2) SRK series
Indoor unit display panel
Error code
Red LED
RUN light
Keeps flashing
Outdoor control PCB Outdoor inventer PCB
Red LED Green LED
Yellow LED
Keeps
1 time flash
flashing
Keeps
1 time flash
flashing
Keeps
Keeps
flashing
1 time flash
flashing
Keeps
1 time flash
flashing
Keeps
1 time flash
flashing
Keeps
1 time flash
flashing
Keeps
1 time flash
6 times flash
flashing
Keeps
1 time flash
1 time flash
flashing
Keeps
1 time flash
flashing
Keeps
1 time flash
flashing
Keeps
flashing
Keeps
1 time flash
flashing
Keeps
1 time flash
6 times flash
flashing
Keeps
1 time flash
flashing
Keeps
Keeps
1 time flash
flashing
flashing
Keeps
1 time flash
flashing
5 times
Keeps
Stays OFF
flash
flashing
Outdoor unit control PCB
Green LED
Red LED
Green LED
Stays OFF
Keeps flashing • Communication error (Defective communication circuit on the main unit of SC-SL2N-E or SC-SL3N-E) ete.
Outdoor unit control PCB
TIMER light
Red LED
Green LED
Stays OFF
Keeps flashing • Communication error (Defective communication circuit on the main unit of SC-SL2N-E or SC-SL3N-E) ete.
Location of trouble
Installation or operating
• Higher outdoor heat exchanger temperature
condition
Outdoor heat exchanger
• Defective outdoor heat exchanger temperature thermistor
temperature thermistor
*• Defective outdoor control PCB (Defective temperature thermistor input
Outdoor control PCB
circuit)?
Installation or operating
• Higher discharge temperature
condition
temperature thermistor • Defective discharge pipe temperature thermistor
*• Discharge pipe Defective outdoor control PCB (Defective temperature thermistor input
Outdoor control PCB
circuit)?
Outdoor heat exchanger
• Defective outdoor heat exchanger temperature thermistor, broken wire or poor
temperature thermistor
connector connection
*• Defective outdoor control PCB (Defective temperature thermistor input
Outdoor control PCB
circuit)?
Outdoor air temperature
• Defective Outdoor air temperature thermistor, broken wire or poor connector
thermistor
connection
*• Defective outdoor control PCB (Defective temperature thermistor input
Outdoor control PCB
circuit)?
Discharge pipe
• Defective discharge pipe temperature thermistor, broken wire or poor
temperature thermistor
connector connection
*• Defective outdoor control PCB (Defective temperature thermistor input
Outdoor control PCB
circuit)?
Installation or operating
• Rising high pressure (Operation of 63H1) • Service valve closing operation
condition
Outdoor control PCB
*• Defective outdoor control PCB (Defective 63H input circuit)?
Inverter PCB or radiator
• Power transistor overheat
fin
Outdoor control PCB
• Current cut (Anomalous compressor over-current)
compressor
Installation or operating
• Service valve closing operation
condition
Outdoor control PCB
• Anomalous outdoor control PCB communication
Inverter PCB
• Anomalous inverter PCB communication
Outdoor fan motor
• Anomalous outdoor fan motor
Outdoor control PCB
*• Defective outdoor control PCB (Defective motor input circuit)?
Installation or operating
• Low pressure error • Service valve closing operation
condition
• Anomalous low pressure, broken wire of low pressure sensor or poor
Low pressure sensor
connector connection
Outdoor control PCB
*• Defective outdoor control PCB (Defective sensor input circuit)?
Inverter PCB
• Anomalous inverter PCB
Suction pipe
• Defective suction pipe temperature thermistor, broken wire or poor connector
temperature thermistor
connection
Outdoor control PCB
*• Defective outdoor PCB (Defective thermistor input circuit)?
Low pressure sensor
• Defective low pressure sensor
Outdoor control PCB
• Defective outdoor control PCB (Defective sensor input circuit)?
Operation status
• Shortage in refrigerant quantity
Installation status
• Service valve closing operation
Compressor,
•Anomalous compressor startup
inverter PCB
Description of trouble
Description of trouble
330
-
-
Description of trouble
'12 • PAC-T-174
Reference
Repair method
page
Repair
Replacement of
434
temperature thermistor
Replacement of PCB
Repair
Replacement, repair of
435
temperature thermistor
Replacement of PCB
Replacement, repair of
temperature thermistor
436
Replacement of PCB
Replacement, repair of
temperature thermistor
437
Replacement of PCB
Replacement, repair of
temperature thermistor
438
Replacement of PCB
Repair
439
Replacement of PCB
Replacement of PCB
440
or Repair
Replacement of PCB
441 ・ 442
Repair
Replacement of PCB
443
Replacement, repair
444
Replacement of PCB
Repair
Replacement, repair of
445 ・ 446
sensor
Replacement of control
PCB
447
Replacement of PCB
Replacement, repair of
temperature thermistor
448
Replacement of control
PCB
Replacement of sensor
449
Replacement of control
PCB
Repair
450
Service valve opening
check
Replacement
451 ・ 452
Repair method
Replacement
Repair method
Replacement