7. OPTIONAL PARTS
8. OPTIONAL PARTS
7-3. JOINT KIT CMY-R160C-J FOR BC CONTROLLER
8-3. Joint Adapter Kit
Joint kit "CMY-R160C-J" is used to combine two ports of the BC controller for a PURY-HP-T(S)KMU/Y(S)KMU system to enable
Joint adapter kit "CMY-R160C-J" is used to combine two ports of the BC controller for a PURY-HP-T(S)KMU/Y(S)KMU system to enable
Indoor capacity above P54 as shown in Fig. 1.
Indoor capacity above P54 as shown in Fig. 1.
The Joint kit include following items:
1 Instructions
2 Joint pipe
(for liquid side)
1pc
1pc
2 Joint pipe (for liquid side)
1. Designing CMY-R160C-J to a PURY-HP-T(S)KMU/
Y(S)KMU system
The maximum of Indoor capacity for one port of BC controller
is P54. When the Indoor capacity is above P54, Joint kit CMY-
R160C-J is needed to combine two ports of BC controller to en-
large the capacity, like Groups 2 and 3 in Fig. 1.
A maximum of three Indoor units are allowed to connect to one
port of BC controller or two combined ports of BC controller us-
ing CMY-R160C-J.
When connecting Indoor units to one port of BC controller or
two combined ports of BC controller using CMY-R160C-J,
CMY-Y102SS-G2 or CMY-Y104C-G is applicable, like Groups
1 and 2 in Fig. 1
Caution: Simultaneous operation of cooling and heating
modes for Indoor units connecting to the same BC ports is not
available.
2. Piping at the installation site
Refer to Fig. 2 for connecting the CMY-R160C-J to the BC controller and the pipe leading to the Indoor units. Non-oxidized brazing
is necessary. Avoid getting foreign material inside the piping.
After piping and air-tight testing, insulate the joint and pipe. Details are available in the Installation Manual.
2
Joint pipe (for liquid side)
Piping to indoor unit
(Non-oxidized brazing)
Fig.2. Connecting CMY-R160C-J
© 2014 Mitsubishi Electric US, Inc.
3 Joint pipe
4 Cover 1
(for gas side)
1pc
2pcs
OUTDOOR UNITS
PURY-HP-T(S)KMU,-Y(S)KMU (September 2014)
5 Cover 2
6 Cover 3
(for gas side)
(for liquid side)
1pc
1pc
3 Joint pipe (for gas side)
OU
PURY-HP-T(S)KMU/Y(S)KMU
CMY-Y102SS-G
IU
IU
IU
Group1
Total Indoor Capacity
<=P54
IU
IU
Group2
Total Indoor Capacity
P55 to P96
Fig.1. CMY-R160C-J applying scheme
Flare nut
3/8" (9.52)
Clamping torque 35N•m
Use two spanners simultaneously for tightening.
Coat the flare contact surface with refrigerating machine oil.
Flare nut
5/8" (15.88)
Clamping torque 80N•m
Use two spanners simultaneously for tightening.
Coat the flare contact surface with refrigerating machine oil.
Joint pipe(for gas side)
3
DATA U10
7 Band
8 Reducer
8pcs
2pcs
in.(mm)
BC controller
Joint kit
CMY-R160C-J
IU
IU
Group3
Total Indoor Capacity
P72 or P96
2 - 477
H2i-R2-259