Service P.c. Board Selection Information - Toshiba RAS-M10SMUV-E Service Manual

Indoor unit
Hide thumbs Also See for RAS-M10SMUV-E:
Table of Contents

Advertisement

11-8. Service P.C. Board Selection Information

[4-way air discharge cassette type]
Service P.C. board selection corresponded table (Main P .C. board MCC-5056)
The indoor control P .C. board (MCC-5056) can correspond to multiple models. When replacing P .C. board
assembly, set the DIP switch and jumper according to the following description.
Switch set up
Function details
SW
Bit
SW01
Bit1-4
TS ADJUST
Bit1, 2
FAN setting
Bit 3
Auto restart
SW02
Remote controller
Bit 4
A/B setting
Jumper setup
1.
J800, J801, J802, J803 : For the following models, set up jumpers according to the table.
Model name
RAS-M10SMUV-E
RAS-M10SMUCV-E
Part No.
J803
J802
J801
J800
FAN 1
FAN 2
RE-
START
RC A/B
A
B
Tel: 01823 665660
Heronhill - for all your Toshiba requirements
Function
Description
Match to set up
contents of P .C. board
before replacement.
RAS-M13SMUV-E
RAS-M13SMUCV-E
¡
¡
¡
¡
J803
J802
J801
J800
< MCC-5056 >
www.heronhill.co.uk
Remarks
OFF: Auto restart is invalid.
ON: Auto restart is valid.
OFF: Remote controller A setting
ON: Remote controller B setting
¡
: Provided (Original)
RAS-M16SMUV-E
RAS-M16SMUCV-E
¡
¡
¡
¡
¡
×
¡
×
– 72 –
Status at shipment
from factory
All ON
All OFF
OFF
OFF
×
: None (Cut)
Status at shipment
from factory
¡
¡
¡
¡
J803
J802
J801
J800
Fax: 01823 665807