Item
14. Auto restart
This product is designed so that, after a power failure, it can restart automatically in the same
function
operating mode as before the power failure.
The product was shipped with Auto Restart function in the OFF position.
Turn it ON as required.
<How to set the Auto Restart>
• Remove the cover of the electric parts box by taking off the mounting screws (3 positions) and
pushing the hooking section. (The cover of the electric parts box remains hanged to the hinge.)
• There are the selector switches (SW02) on the P.C. board of the electric parts box.
No.3 of the selector switches (SW02) is provided for the selector switch. Select ON of No.3 of the
selector switches (SW02). (OFF: setting without Auto Restart, ON: setting with Auto Restart)
15. High ceiling
<How to set the High ceiling switch>
select switch
• Remove the cover of the electric parts box by taking off the mounting screws (3 positions) and
pushing the hooking section. (The cover of the electric parts box remains hanged to the hinge.)
• There are the selector switches (SW02) on the P.C. board of the electric parts box.
No.1 and No.2 of the selector switches (SW02) are provided to select the height of the ceiling.
According to the ceiling height in the following table, select No.1 or No.2 of the selector switches
(SW02).
M10SMUV-E, M10SMUCV-E,
M13SMUV-E, M13SMUCV-E
M16SMUV-E, M16SMUCV-E
<Height list of ceiling possible to be installed>
Standard (Factory setting)
High ceiling (1)
High ceiling (2)
Tel: 01823 665660
Heronhill - for all your Toshiba requirements
Operation flow and applicable data, etc.
Model
Possible installed
RAS-
ceiling height
Up to 2.7 m
Up to 3.5 m
M10SMUV-E
Model
RAS-
M10SMUCV-E
2.5 to 2.7 m
www.heronhill.co.uk
INFORMATION
When using the high ceiling (1) or (2),
cold air may be felt due to the
temperature drop of discharge air.
M13SMUV-E
M13SMUCV-E
2.5 to 2.7 m
– 35 –
Description
ON
6H
SW01
1
2 3 4
TS ADJUST
ON
ON
6H
ON
SW02
OFF
1
2 3 4
REMARKS
M16SMUV-E
SW02
M16SMUCV-E
No.1
No.2
2.5 to 2.9 m
OFF
OFF
2.9 to 3.2 m
ON
OFF
3.2 to 3.5 m
ON
ON
ON
6H
1
2 3 4
SW01
TS ADJUST
ON
ON
6H
ON
SW02
OFF
1
2 3 4
Fax: 01823 665807

Advertisement

Table of Contents
loading

Table of Contents