Evacuating the connected pipes

Adding Refrigerant

Add refrigerant charge according to table below:
If you use a pipe longer than 5 m,
'A' g of refrigerant R-410A must be added for each extra meter.
If you use a pipe shorter than 5 m,
The evacuating time is normal.
Refer to the Service Manual for further details.
• T he remaining air in the Refrigeration cycle, which contains moisture, may cause malfunction on the compressor.
• A lways contact the service center or a professional installation agency for product installation.
NA_BETTER_A3050_IB&IM_EN_DB68-04388A-00.indd 47
English-47