Boiler Water Temp; Flow Temperature - Viessmann VITOLADENS333-F Service Instructions Manual

Type vp3s, 12.9/19.3 kw, 16.1/23.5 kw oil fired compact condensing boiler, for the combustion of low sulphur fuel oil din 51603-el-1
Table of Contents

Advertisement

Fault codes
(cont.)
Fault code
System character-
on the dis-
istics
play
20
Regulates without

flow temperature

sensor (low loss
header)
28
Regulates without
flow temperature
sensor (low loss
header)
30
Burner blocked
38
Burner blocked
40
Mixer closes
48
Mixer closes
50
No DHW heating
58
No DHW heating
A7
Control mode as per
delivered condition
b0
Burner blocked
b1
Control mode as per
delivered condition
Cause
Measures
System flow tem-
Check the low loss
perature sensor
header sensor (see
shorted out
page 75).
System flow tem-
Check the low loss
perature sensor
header sensor (see
lead broken
page 75).
Boiler water tem-
Check the boiler water
perature sensor
temperature sensor (see
shorted out
page 75).
Boiler water tem-
Check the boiler water
perature sensor
temperature sensor (see
lead broken
page 75).
Heating circuit
Check the flow tempera-
with mixer M2
ture sensor.
flow temperature
sensor shorted
out
Heating circuit M2
Check the flow tempera-
flow temperature
ture sensor.
sensor lead bro-
ken
Cylinder tempera-
Check the sensor (see
ture sensor
page 75).
shorted out
Cylinder tempera-
Check the sensor (see
ture sensor lead
page 75).
broken
Faulty program-
Replace the program-
ming unit
ming unit.
Flue gas tem-
Check the flue gas tem-
perature sensor
perature sensor (see
shorted out
page 77).
Communication
Check connections and
fault; program-
replace the program-
ming unit (inter-
ming unit if required.
nal)
Troubleshooting
69