Troubleshooting
Fault display
(cont.)
Calling up acknowledged fault messages
Press the following keys:
1. d
for approx. 3 s.
Calling up fault codes from the fault memory (fault history)
The 10 most recent faults are saved
and may be scanned.
The faults are ordered by date, thus
the most recent fault is fault number 1.
Fault codes
Fault code
System character-
on the dis-
istics
play
0F
Control mode
10
Regulates as if the

outside temperature

was 0 °C
18
Regulates as if the
outside temperature
was 0 °C
68
2. a/b for the acknowledged fault.
Press the following keys:
1. G + d simultaneously for
approx. 2 s.
2. a/b
for individual fault
codes.
3.
Note
All saved fault codes can be
deleted with e.
4. d
Scanning is completed.
Cause
Measures
Maintenance
Service the equipment.
After the service, set
coding address "24:0".
Outside tempera-
Check the outside tem-
ture sensor
perature sensor (see
shorted out
page 74).
Outside tempera-
Check the outside tem-
ture sensor lead
perature sensor (see
broken
page 74).