Slant/Fin Victory VSP-60 Installation And Operating Instructions Manual page 7

Hide thumbs Also See for Victory VSP-60:
Table of Contents

Advertisement

V
ICTORY VSP Models
Maximum allowed flue and air intake equivalent length (Feet)
Boiler Model
Maximum allowed flue and air intake equivalent length (Feet)
Boiler Model
Maximum allowed flue and air intake equivalent length (Feet)
Boiler Model
Heat-Fab Saf-T vent system (Including EZ-Seal)
0 - 5,000 Ft.
Piping
Number
VSP-60
Flue
Air Intake
VSP-90
Flue
Air Intake
VSP-120
Flue
Air Intake
VSP-150
Flue
Air Intake
VSP-180
Flue
Air Intake
Z-Flex Z-Vent and Flex-L StaR-34 vent systems
0 - 5,000 Ft.
Piping
Number
VSP-60
Flue
Air Intake
VSP-90
Flue
Air Intake
VSP-120
Flue
Air Intake
VSP-150
Flue
Air Intake
VSP-180
Flue
Air Intake
ProTech FasNSeal vent systems
0 - 5,000 Ft.
Piping
Number
VSP-60
Flue
Air Intake
VSP-90
Flue
Air Intake
VSP-120
Flue
Air Intake
VSP-150
Flue
Air Intake
VSP-180
Flue
Air Intake
for
5,000 - 7,500 Ft.
Elevation
Elevation
40
40
40
40
40
40
40
40
40
35
40
40
35
30
40
40
33
28
40
35
for
5,000 - 7,500 Ft.
Elevation
Elevation
35
35
40
40
35
35
40
40
35
30
40
40
30
25
40
40
28
23
40
35
for
5,000 - 7,500 Ft.
Elevation
Elevation
30
30
40
40
30
30
40
40
30
25
40
40
25
20
40
40
23
18
40
35
7,500 - 10,000 Ft.
Elevation
40
40
35
40
30
40
25
35
23
30
7,500 - 10,000 Ft.
Elevation
35
40
30
40
25
40
20
35
18
30
7,500 - 10,000 Ft.
Elevation
30
40
25
40
20
40
15
35
15
30
7