Section 7: Appliance Set-Up; Outside Air Installation - Quadra-Fire GRAND-MBK-AU Owner's Manual

Hide thumbs Also See for GRAND-MBK-AU:
Table of Contents

Advertisement

Voyageur Grand
7
Appliance Set-up
Remove the zip tie to the lower
access cover. It is to prevent the
cover opening during shipping.
A. Outside Air Kit Installation
A source of air (oxygen) is necessary in order for combustion to
take place. Whatever combustion air is consumed by the fi re
must be replaced. Air is replaced via air leakage around win-
dows and under doors. In homes that have tightly sealed doors
and windows, an outside air source is needed. An optional Out-
side Air Kit is available.
Items Needed for Installation (not supplied)
• 102 millimeter fl ex aluminum pipe, or if using alternate mate-
rial, then it shall be made from durable, non-combustible,
heat resistant material up to 177°C. Cut the pipe to the
required length for your installation.
• Phillips head screw driver
• Silicone sealant
Option One - Outside Air Installation Instructions
1. Swing grille down to expose the two screws. Figure
19.1
2. Remove the two screws and pull the access assembly
away from the appliance.
3. Assemble the outside air cover plate A supplied in com-
ponent pack.
4. Re-install the access assembly.
5. Remove the outside air cover plate B on outer can and dis-
card. Figure 19.2
6. Install optional fl ex adapter to outer can with the same
screws. Do not use plastic wire ties that come with the kit as
they will melt. NOTE: You may need to install the fl ex pipe
into the fi rebox fi rst depending on installation. Attach fl ex to
adapater with at least 2 screws.
7. Ensure existing access hole in fi replace is suffi cient to feed
the 102 mm fl ex.
8. After sliding can into fi replace, feed fl ex into cut opening to
obtain outside combustion air.
9. Level outer can and install appliance. See page 20.
Option Two - Outside Air Installation Instructions
1. Follow steps 1-5 in Option One above
2. Ensure existing acces hole in fi replace will not be covered by
the outer can. Existing outside air intake hole may be under
at the rear or side of outer can. Outside air may also enter
down existing chimney chase in some situations.
3. Repeat step 9 under Option One with one exception. After
installing the appliance in the outer can, seal the fi replace
opening and trim package with insulation to prevent air leak-
age into the room.
Page 22
Fire Risk
Asphyxiation Risk
Do not draw outside combustion air from:
Fumes or odor may result
Asphyxiation Risk
Outside air inlet must be located to prevent blockage from:
Leaves, snow, ice or other debris
Block may cause combustion air starvation
Smoke spillage may set off alarms or irritate sensitive indi-
viduals.
Asphyxiation Risk
Length of outside air supply duct shall NOT exceed
the length of the vertical height of the exhaust fl ue.
• Fire will not burn properly
• Smoke spillage occurs when door is opened due
to air starvation.
Grille hinges
downward
Remove Screws &
Pull Access Assembly
away from Insert
Figure 19.1
Figure 19.2
7075-205B
WARNING
Wall, fl oor or ceiling cavity
Enclosed space such as an attic or garage
Close proximity to exhaust vents or
chimneys
WARNING
WARNING
Remove Outside Cover
Plate A (Discard)
Outside Air Cover
Plate B (Discard)
Flex Adapter
October 12, 2015
Termination
Cap

Advertisement

Table of Contents
loading

Table of Contents