3
CONNECT RANGE CORD
Ranges are dual rated for use on either 120/240 VAC or 120/208
VAC. See table for power ratings and circuit breaker sizes based
upon the supply voltage for each mode (See chart at left).
This appliance may be connected to the power supply by installing
flexible conduit or a power cord set. The electrical rating of the
power cord set (not supplied) must be 120/240 volt, 50 amperes
minimum for models HES. The power cord set shall be marked
"For Use with Ranges."
The power supply shall be connected to the range terminal block
compartment located in the lower left rear corner, accessible by
removing the storage drawer below the oven.
Remove the terminal box cover by removing the cover screw.
Install the proper connector in knockout(s) provided. The electrical
supply, including connectors or power cord, can lie anywhere
within the shaded area (See Figure 2.)
Electrical Connection Procedures
Refer to Figure 4 and Figures A, B, C, D & E (next page) for further explanation.
CONSULT YOUR INSTRUCTIONS FOR 'ELECTRICAL CONNECTION PROCEDURES'. COPPER WIRE MUST BE USED
FOR CONNECTION TO THE TERMINAL BLOCK. WHEN POWER SUPPLY CORD KIT IS USED TO CONNECT RANGE TO
THE POWER SUPPLY. USE ONLY CORD KITS RATED 125/240 VOLTS MINIMUM AND MARKED FOR USE WITH RANGES.
REFER TO INSTALLATION INSTRUCTIONS FOR PROPER CORD KIT AMPERAGE RATING, RISK OF FIRE OR
ELECTRICAL SHOCK MAY BE INCURRED IF AN INCORRECT SIZE RANGE CORD KIT IS USED, THE INSTALLATION
INSTRUCTIONS ARE NOT FOLLOWED, OR THE STRAIN RELIEF BRACKET IS DISCARDED.
RISK OF ELECTRIC SHOCK FRAME GROUNDED TO NEUTRAL OF APPLICANCE THROUGH A LINK GROUNDING
THROUGH THE NEUTRAL CONDUCTOR IS PROHIBITED FOR NEW BRANCH-CIRCUIT INSTALLATIONS. (1996 NEC)
MOBILE HOMES AND RECREATIONAL VEHICLES, OR IN AN AREA WHERE LOCAL CODES PROHIBIT GROUNDING
THROUGH NEUTRAL CONDUCTOR. FOR INSTALLATIONS WHERE GROUNDING THROUGH THE NEUTRAL CONDUC-
TOR IS PROHIBITED:
(1) DISCONNECT THE LINK FROM THE NEUTRAL.
(2) USE GROUNDING TERMINAL OR LEAD TO GROUND UNIT: AND
(3) CONNECT NEUTRAL TERMINAL OR LEAD TO BRANCH CIRCUIT NEUTRAL IN USUAL MANNER
(WHEN THE APPLIANCE IS CONNECTED BY MEANS OF A CORD KIT, USE 4 CONDUCTOR
CORD FOR THIS PURPOSE).
Center or white wire
must always be
attached to the
central terminal on
block.
All screw and nut
connections must be
tight.
Figure 4

STEP 3: CONNECT RANGE CORD

MODEL HES23
MODEL HES24, HES25
WARNING
Page 4
VOLTS
H Z
A.C.
120/240
60
120/208
60
VOLTS
HZ
A.C.
120/240
60
120/208
60
Remove ground
strap from terminal
block. Install with
care, the green
ground wire as
shown at left. Attach
ground wire and
strap with screw
provided with strap.
RATING
CIRCUIT
K W
BREAKER
12.1
50 AMPS
9.1
45 AMPS
RATING
CIRCUIT
KW
BREAKER
12.6
50 AMPS
9 . 5
50 AMPS