Auto Line Correcting; How To Activate This Function; Led Indication During Detection; Led Indication After Detection - Mitsubishi Electric MXZ-2B20NA Service Manual

Hide thumbs Also See for MXZ-2B20NA:
Table of Contents

Advertisement

10-2. AUTO LINE CORRECTING <MXZ-3B24NA, MXZ-3B30NA, MXZ-4B36NA, MXZ-5B42NA>
Outdoor unit has an auto line correcting function which automatically
detects and corrects improper wiring or piping.
Improper wiring or piping can be automatically detected by pressing the piping/wiring correction switch (SW871).
When improper wiring or piping is detected, wiring lines are corrected.
This will be completed in about 10 to 20 minutes.

[How to activate this function]

1. Check that outside temperature is above 32˚F.
(This function does not work when outside temperature is not above 32˚F.)
2. Check that the stop valves of the liquid pipe and gas pipe are open.
3. Check that the wiring between indoor and outdoor unit is correct.
(If the wiring is not correct, this function does not work.)
4. Turn ON the power supply and wait at least 1 minute.
5. Press the piping/wiring correction switch (SW871) on the electronic control P.C. board.
Do not touch energized parts.

LED indication during detection:

LED1 (Red)
LED2 (Yellow)
Lighted

LED indication after detection:

LED1 (Red)
LED2 (Yellow)
Lighted
Once
Other indications
Make sure that the valves are open and the pipes are not collapsed or clogged.
6. Press the switch to cancel.
LED indication after cancel :
LED1 (Red)
LED2 (Yellow)
Lighted
NOTE : Indoor unit cannot be operated while this function is activated.
When this function is activated while indoor unit is operating, the operation will be stopped.
Operate indoor unit after the auto line correcting is finished.
Pressing the switch during detection cancels this function.
The record of auto line correcting can be confirmed in the following way:
Press the switch for more than 5 seconds.
LED will show the record of auto correcting for about 30 seconds as shown in the table below:
Number of blinks
LED1 (Red)
LED2 (Yellow)
Once
3 times
NOTE : Activate this function to confirm the correct wiring after replacing the electronic control P.C. board.
(Previous records are deleted when the electronic control P.C. board is replaced.)
The record cannot be shown if auto line correcting is not canceled (Refer to "How to activate this function").
OBH560G
LED3 (Green)
Lighted
Once
LED3 (Green)
Not lighted
Lighted
Once
Once
LED3 (Green)
Lighted
Not lighted
LED3 (Green)
Once
Lighted
3 times
Lighted
Indication
Completed (Problem corrected/ nomal)
Not completed (Detection failed)
Refer to "SAFETY PRECAUTIONS WHEN LED FLASHES"
located behind the service panel.
Wiring line
Not corrected
Corrected
55