Fin temperature thermistor
Ambient temperature thermistor
Outdoor heat exchanger temperature
Capacity code
10
SERVICE FUNCTIONS
MXZ-2B20NA MXZ-3B24NA MXZ-3B30NA MXZ-4B36NA MXZ-5B42NA
10-1. PRE-HEAT CONTROL
If moisture gets into the refrigerant cycle, or when refrigerant is liquefied and collected in the compressor, it may interfere
the start-up of the compressor.
To improve start-up condition, the compressor is energized even while it is not operating.
This is to generate heat at the winding.
The compressor uses about 50 W when pre-heat control is turned ON.
Pre-heat control is ON at initial setting.
[How to deactivate pre-heat control]
Turn OFF the power supply for the air conditioner before making the setting.
Set the "4" of SW1 on the electronic control P.C. board to ON to deactivate pre-heat control function (MXZ-2B20NA).
Set the "4" of SW2 on the electronic control P.C. board/outdoor control P.C. board to ON to deactivate pre-heat control
function (MXZ-3B24NA, MXZ-3B30NA, MXZ-4B36NA, MXZ-5B42NA).
MXZ-2B20NA
Electronic control
P.C. board
Turn ON the power supply for the air conditioner.
NOTE: Pre-heat control will be turned OFF when the breaker is turned OFF.
OBH560G
Purpose
Compressor
Protection
Defrosting Protection
Defrosting
Protection
Control
Protection
Control
MXZ-3B24NA
MXZ-3B30NA
MXZ-4B36NA
SW2
ON
SW2
SW1
SW871
1 2 3 4 5 6
SW2
ON
Electronic control
P.C. board
1 2 3 4 5 6
54
Actuator
Outdoor
4-way
LEV
fan motor
valve
MXZ-5B42NA
Outdoor control P.C. board
Solenoid
valve
(MXZ-5B)