C. Termination Requirements
Install a cap approved and listed for this fireplace system.
Locate cap where it will not become plugged by snow or other materials.
Locate cap away from trees or other structures.
The bottom of the termination cap must be at least 3 ft (.91 m) above the roof AND at least 2 ft (.61 m) above any portion
of roof within 10 ft (3.05 m).
Slanted Roofs
Chimney must
extend 3 ft (.9 m)
above the roof
Flat Roofs
Chimney must
extend 3 ft (.9 m)
above the roof
Figure 4.3
Termination Cap Locations
Heatilator • MEL36, MEL42 Installation Manual • 4044-212 • Rev D • 01/06/15
Chimney must extend 2 ft (.6 m)
above any portion of the roof or
adjacent structures within
10 ft (3 m) of the chimney
Chimney must extend 2 ft (.6 m)
above any portion of the roof or
adjacent structures within
10 ft (3 m) of the chimney
13