Others - Toshiba RAS-13UKPX-T2 Service Manual

Split wall type
Table of Contents

Advertisement

2. Set the remote control selector switch with the
remote control
[B] is indicated on the liquid crystal display when
setting remote control selector switch to B. [A] is not
indicated on the display even if the selector switch
is set to A.
1) Load the remote control with the batteries.
2) Press the [CHECK] button using something with
sharp point. (The preset temperature on the remote
control changes to [00].)
3) Press the [MODE] button while pressing the
[CHECK] button, [B] is indicted at the right of the
present temperature display.
• To reset the switch to the [A] setting, press the
[MODE] button again while pressing the [CHECK]
button.
A
B
PRESET
START/STOP
AUTO
FAN
MODE
SWING
ECO
Hi-POWER
TIMER
FIX
MEMO
ON
OFF
SET
CLR
FILTER
RESET
CLOCK CHECK
Fig. 8-6-2
3. Confirm that the indoor unit can operate with
the new setting.

8-7. Others

8-7-1. Gas leak test
For RAS-10UASX, RAS-07UAX-T2
For RAS-13UAX-T2, RAS-10UAX-T2
A
B
Flare nut connections
(Outdoor unit)
[MODE] button
• Check the flare nut connections, valve stem cap
[CHECK] button
8-7-2. Test operation
To switch the TEST RUN (COOL) mode, press
TEMPORARY button for 10 sec.
(The beeper will make a short beep.)
– 42 –
Valve stem cap
connection
Service cap
connection
Fig. 8-7-1
Electric parts cover
Fig. 8-7-2
connections and service port cap connections for
gas leak with a leak detector or soap water.
TEMPORARY button
TEMPORARY button
Fig. 8-7-3
FILE NO. SVM-02003
Valve cover
C
D
Flare nut connections
(indoor unit)
Valve stem cap
connection
A
Service cap
B
connection
Valve stem cap connection