7-2-3. Dry operation
([MODE] button on the remote control is set
to the dry operation.)
(1) The compressor, outdoor fan and operation
display on the remote control are controlled as
shown in Fig. 7-2-4.
+3
+2
+1
Preset
0
temp.
Fig. 7-2-4
(2) The microcontroller turns the compressor on and
off at the regular intervals (4 to 6 minutes). While
the compressor is turning off, the indoor fan motor
operates in the SUPER LOW position.
The pattern of operation depending on the relation
between room temperature and preset
temperatures is shown in Fig. 7-2-5.
Room temp.
Preset temp.+1
Preset temp.
ON
Compressor
Outdoor fan
OFF
*
Indoor fan
L.
S.L.
*
Super Low
Fig. 7-2-5
(3) [FAN] button on the remote control is set to AUTO
only.
(4) The Hi POWER operations cannot be set.
ON
OFF OFF
ON
ON
ON
OFF
OFF
L.
S.L.
L.
S.L.
L.
7-2-4. Automatic operation
([MODE] button on the remote control is set
to the automatic operation.)
(1) One of 2 operations (Cooling, Fan only) is
selected according to difference between the
preset temperature and the room temperature at
which the automatic operation has started, as
shown in Fig. 7-2-6. The Fan only operation
continues until the room temperature reaches a
level at which another mode is selected.
(2) Temporary Auto
When the TEMPORARY button on the indoor unit
is pushed, the preset temperature is fixed at 24°C
and the indoor unit is controlled as shown in
Fig. 7-2-6.
°C
The louver moves to the position same
as Hi POWER operation.
+4
0
RAS-13UKPX-T2, RAS-13UKX
RAS-10UKPX-T2, RAS-10UKX
RAS-07UKPX-T2
– 23 –
FILE NO. SVM-02003

Cooling operation

Cooling operation

Fan only operation

Fig. 7-2-6