Lp Conversion - Rheem (-)802PA050314MSA Installation Instructions Manual

Upflow/horizontaltwo stage gas furnaces
Table of Contents

Advertisement

NOTE: The valve can be converted to use liquified petroleum
(LP) gas by replacing the pressure regulator spring with the
conversion kit spring. This LP kit spring allows the regulator
to maintain the proper manifold pressure for LP gas. See
Figure 21.
NOTE: Order the correct LP conversion kit from the furnace
manufacturer. Furnace conversion to LP gas must be per-
formed by a qualified installer, service agency or the gas
supplier.
NOx MODELS
When converting furnaces equipped with NOx inserts to LP gas,
remove the NOx insert assemblies. Steps for removal are listed
below:
1. Turn off all electrical power and the gas supply to the furnace.
2. Remove the burner door from the furnace.
3. Remove the burner assembly – handle with care.
4. Remove the two screws attaching the NOx insert retainer
bracket to the center panel and remove NOx inserts.
5. Put the two screws back into the holes in the center panel.
6. Re-install the burner assembly.
7. Replace burner door.
8. Turn on electrical power and gas supply to the unit.
NOTE: Some NOx models may have one less NOx insert.
ORIFICE INSTALLATION
LP Gas is a manufactured gas that has consistent heating
value across most regions.
The Sea Level input should still be reduced by 4% per
thousand ft. and the orifice size must be selected based on
the reduced input selection chart in High Alt. Instruction
Section.
To change orifice spuds for either conversion to LP or for el-
evation:
1. Shut off the manual main gas valve and remove the
gas manifold.
2. Replace the orifice spuds.
3. Reassemble in reverse order.
TABLE 7
LP GAS PIPE CAPACITY TABLE (CU. FT./HR.)
Maximum capacity of pipe in thousands of BTU per hour of undiluted liquefied petroleum gases (at 11 inches water
column inlet pressure).
(Based on a Pressure Drop of 0.5 Inch Water Column)
Nominal
Iron Pipe
Size, Inches
10
20
30
1/2
275
189
152
3/4
567
393
315
1
1,071
732
590
1-1/4
2,205
1,496
1,212 1,039
1-1/2
3,307
2,299
1,858 1,559
2
6,221
4,331
3,465 2,992
Example (LP): Input BTU requirement of unit, 120,000
Equivalent length of pipe, 60 ft. = 3/4" IPS required.

LP CONVERSION

4. Turn the gas supply back on and check for proper oper-
ation and manifold pressure.
5. Attach the notice label alerting the next service techni-
cian that the furnace has been converted to LP gas.
LP TANKS FROM LOCAL LP SUPPLIER MUST NOT
BE USED TO STORE ANYTHING (SUCH AS FERTIL-
IZER) EXCEPT LP GAS. THIS INCLUDES ALL DELIV-
ERY VESSELS (LP TRUCKS). IF MATERIAL OTHER
THAN LP GAS IS USED IN THE SAME
VESSELS/TANK AS THE LP GAS, THE LP GAS CAN
BECOME CONTAMINATED AND DAMAGE THE FUR-
NACE. THIS WILL VOID THE MANUFACTURER'S
WARRANTY. CONTACT THE SUPPLIER TO MAKE
SURE FERTILIZER IS NOT USED IN THE SAME
TANKS USED TO STORE AND DELIVER LP GAS.
FIGURE 21
TYPICAL LP KIT CONTENTS
Length of Pipe, Feet
40
50
60
70
80
129
114
103
96
89
267
237
217
196
182
504
448
409
378
346
913
834
771
724
1,417
1,275
1,181
1,086 1,023
2,646
2,394
2,205
2,047 1,921
90
100
125
150
83
78
69
63
173
162
146
132
322
307
275
252
677
630
567
511
976
866
787
1,811 1,606
1,496
27

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents