Lp Conversion; Nox Models; Orifice Installation - Rheem 80MDV SERIES Installation Instructions Manual

Upflow/horizontal two stage, communicating gas furnaces w/ecm blower
Table of Contents

Advertisement

TABLE 7
LP GAS PIPE CAPACITY TABLE (CU. FT./HR.)
Maximum capacity of pipe in thousands of BTU per hour of undiluted liquefied petroleum gases (at 11 inches water
column inlet pressure).
(Based on a Pressure Drop of 0.5 Inch Water Column)
Nominal
Iron Pipe
Size, Inches
10
20
30
1/2
275
189
152
3/4
567
393
315
1
1,071
732
590
1-1/4
2,205
1,496
1,212 1,039
1-1/2
3,307
2,299
1,858 1,559
2
6,221
4,331
3,465 2,992
Example (LP): Input BTU requirement of unit, 120,000
Equivalent length of pipe, 60 ft. = 3/4" IPS required.

LP CONVERSION

LP TANKS FROM LOCAL LP SUPPLIER MUST NOT
BE USED TO STORE ANYTHING (SUCH AS FERTIL-
IZER) EXCEPT LP GAS. THIS INCLUDES ALL DELIV-
ERY VESSELS (LP TRUCKS). IF MATERIAL OTHER
THAN LP GAS IS USED IN THE SAME
VESSELS/TANK AS THE LP GAS, THE LP GAS CAN
BECOME CONTAMINATED AND DAMAGE THE FUR-
NACE. THIS WILL VOID THE MANUFACTURER'S
WARRANTY. CONTACT THE SUPPLIER TO MAKE
SURE FERTILIZER IS NOT USED IN THE SAME
TANKS USED TO STORE AND DELIVER LP GAS.
FIGURE 21
TYPICAL LP KIT CONTENTS
Length of Pipe, Feet
40
50
60
70
80
129
114
103
96
89
267
237
217
196
182
504
448
409
378
346
913
834
771
724
1,417
1,275
1,181
1,086 1,023
2,646
2,394
2,205
2,047 1,921
90
100
125
150
83
78
69
63
173
162
146
132
322
307
275
252
677
630
567
511
976
866
787
1,811 1,606
1,496
27

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

802v series

Table of Contents