Lp Conversion - Rheem 801T Series Installation Instructions Manual

Upflow/horizontal single stage gas furnaces with constant-torque air circulation blower
Table of Contents

Advertisement

GAS PRESSURE
NOTE: The valve can be converted to use liquified petro-
leum (LP) gas by replacing the pressure regulator spring
with the conversion kit spring . This LP kit spring allows the
regulator to maintain the proper manifold pressure for LP
gas . See Figure 21 .
NOTE: Order the correct LP conversion kit from the fur-
nace manufacturer . Furnace conversion to LP gas must
be performed by a qualified installer, service agency or the
gas supplier .
NOx MODELS
When converting furnaces equipped with NOx inserts to LP gas,
remove the NOx insert assemblies . Steps for removal are listed
below:
1 . Turn off all electrical power and the gas supply to the furnace .
2 . Remove the burner door from the furnace .
3 . Remove the burner assembly – handle with care .
4 . Remove the two screws attaching the NOx insert retainer
bracket to the center panel and remove NOx inserts .
5 . Put the two screws back into the holes in the center panel .
6 . Re-install the burner assembly .
7 . Replace burner door .
8 . Turn on electrical power and gas supply to the unit .
NOTE: Some NOx models may have one less NOx insert .
ORIFICE INSTALLATION
LP Gas is a manufactured gas that has consistent heating
value across most regions .
The Sea Level input should still be reduced by 4% per
thousand ft . and the orifice size must be selected based
on the reduced input selection chart in High Alt . Instruction
Section .
To change orifice spuds for either conversion to LP or for
elevation:
1 . Shut off the manual main gas valve and remove the
gas manifold .
2 . Replace the orifice spuds .
3 . Reassemble in reverse order .
TABLE 7
LP GAS PIPE CAPACITY TABLE (CU . FT ./HR .)
Maximum capacity of pipe in thousands of BTU per hour of undiluted liquefied petroleum gases (at 11 inches water column
inlet pressure).
(Based on a Pressure Drop of 0.5 Inch Water Column)
Nominal
Iron Pipe
Size, Inches
Example (LP):
10
20
30
40
1/2
275
189
152
129
3/4
567
393
315
267
1
1,071
732
590
504
1-1/4
2,205
1,496
1,212
1,039
1-1/2
3,307
2,299
1,858
1,559
2
6,221
4,331
3,465
2,992
Input BTU requirement of unit, 120,000
Equivalent length of pipe, 60 ft. = 3/4" IPS required.

LP CONVERSION

4 . Turn the gas supply back on and check for proper op-
eration and manifold pressure .
5 . Attach the notice label alerting the next service techni-
cian that the furnace has been converted to LP gas .
WARNING
!
LP TANKS FROM LOCAL LP SUPPLIER MUST NOT
BE USED TO STORE ANYTHING (SUCH AS FER-
TILIZER) EXCEPT LP GAS . THIS INCLUDES ALL
DELIVERY VESSELS (LP TRUCKS) . IF MATERIAL
OTHER THAN LP GAS IS USED IN THE SAME VES-
SELS/TANK AS THE LP GAS, THE LP GAS CAN
BECOME CONTAMINATED AND DAMAGE THE
FURNACE . THIS WILL VOID THE MANUFACTUR-
ER'S WARRANTY. CONTACT THE SUPPLIER TO
MAKE SURE FERTILIZER IS NOT USED IN THE
SAME TANKS USED TO STORE AND DELIVER LP
GAS .
FIGURE 21
TYPICAL LP KIT CONTENTS
Length of Pipe, Feet
50
60
70
80
90
114
103
96
89
83
237
217
196
182
173
448
409
378
346
322
913
834
771
724
677
1,417
1,275
1,181
1,086
1,023
2,646
2,394
2,205
2,047
1,921
100
125
150
78
69
63
162
146
132
307
275
252
630
567
511
976
866
787
1,811
1,606
1,496
27

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents