Insert Installation; Check Gas Type; Install Gas Piping - Monessen Hearth IDV SERIES IDV380NVC Installation And Operating Instructions Manual

Idv series direct vent gas fireplace insert
Table of Contents

Advertisement

iNSeRt iNStAllAtiON

CheCK GAS tyPe

Use proper gas type for the fireplace you are installing. If you have conflicting gas type, do not install
fireplace. See dealer where you purchased the fireplace for proper fireplace according to your gas
type.
iNStAlliNG GAS PiPiNG tO FiRePlACe lOCAtiON
A qualified installer or service person must
connect appliance to gas supply. Follow
all local codes.
iNStAllAtiON iteMS NeeDeD
Make sure you have the items listed below before installing appliance.
External regulator (supplied by installer)
Sealant (resistant to propane/LP gas)
Tee joint
approved flexible gas line with gas connector (if allowed by local codes — not provided)
* A CSA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test
gauge connection. Purchase the CSA design-certified equipment shutoff valve from your dealer.
For propane/LP connections only, the installer must supply an external regulator. The external regulator will
reduce incoming gas pressure. You must reduce incoming gas pressure to between 11 and 13 inches of wa-
ter. If you do not reduce incoming gas pressure, burner system regulator damage could occur. Install external
regulator with the vent pointing down as shown in Figure 14. Pointing the vent down protects it from freezing
rain or sleet.
External
Regual-
tor
Vent
Pointing
Down
Figure 14 -
External Regulator with Vent Pointing Down
(Propane/LP Only)
57D0016
Piping (check local codes)
Sediment trap (optional but recommended)
Pipe wrench
100 gal. (min.
Propane/LP
Supply Tank
FP1930
IDV380/IDV490 Fireplace Insert
For propane/lP units, never connect
fireplace directly to the propane/lP
supply. this burner system requires an
external regulator (not supplied). install
the external regulator between the burner
system and propane/lP supply.
Test gauge connection*
use only new black iron or steel pipe. inter-
nally tinned copper or copper tubing can be
used per National Fuel Gas Code, Section
2.6.3, providing gas meets hydrogen sulfide
limits, and where permitted by local codes.
Gas piping system must be sized to provide
minimum inlet pressure (listed on data plate)
at the maximum flow rate (Btu/hr). undue
pressure loss will occur if the pipe is too
small.
When using copper or flex connectors use only fittings
approved for gas connections. The gas control inlet is
3/8" NPT.
15