Beckett Burner Calibration - Viessmann VITOROND 100 Installation And Service Instructions Manual

Oil-fired
Table of Contents

Advertisement

Initial Start-Up
(continued)

Beckett burner calibration

Boiler model
Burner model
Fuel type
Pump pressure
Oil nozzle
Oil nozzle
Oil nozzle flow rate
Air tube length
Air tube insertion
Air tube combination
Head type
Head setting
Air setting
Static plate
Baffle
Fuel pump c/w solenoid valve
Flange
IMPORTANT
*1
The Beckett burner for the VR1-63 boiler is shipped with factory setting and oil nozzle installed. For VR1-50 boiler,
replace installed nozzle with nozzle packaged with burner.
*1
Model No.
Beckett
oil
psig
Danfoss
Delavan
Hago
GPH@psig
inches
mm
inches
mm
VR1-40
NX-VI 704
175
0.85x60°AH
0.85x60°A
n.a.
1.15@175
7
178
7
4
/
8
124
NX70LJ
9-slot
3.5
see head setting
n.a.
21844
32073
VR1-50
*1
AFG-VI 801
No. 2 fuel oil
175
n.a.
1.10x45°W
1.10x45°W
1.40@175
9
230
184
AFG90MDAQ
V1
1
10/1
2-3/4U
n.a.
21844
31309
Initial Start-up
VR1-63
*1
AFG-VI 801
175
n.a.
1.35x60°W
1.35x60°B
1.75@175
9
230
184
AFG90MDAQ
V1
4
10/2
2-3/4U
21844
31309
59

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents