Minimum Clearances To Combustibles - Viessmann VITOROND 100 Installation And Service Instructions Manual

Oil-fired
Table of Contents

Advertisement

Set-up

Minimum Clearances to Combustibles

min. 6" / 150 mm
Fig. 4
Fig. 5
Legend
Boiler
Burner
*1
.
Clearance of 24" / 610 mm required for burner service.
14
For typical installations, Viessmann recommends installing the boiler with
clearances as published on page 15 under Recommended Minimum Clearances for
Service.
min. 0" / 0 mm
min.
24"
*1
610 mm
24" Vitotronic
installation
min. 6" / 150 mm
6" Aquastat
installation
min.
24"
*1
610 mm
The following are clearances to
combustibles:
Standard installation
VR1
-40
Boiler
Model
Rear
inches
6
mm
150
Sides
inches
0
mm
0
Flue
inches
9
mm
230
Floor
Combustibles
Alcove installation
VR1
-40
Boiler
Model
Rear
inches
6
mm
150
Sides
inches
0
mm
0
Flue
inches
9
mm
230
Top*
inches
6
mm
150
Floor
Combustibles
-50
-63
6
6
150
150
0
0
0
0
9
9
230
230
-50
-63
6
6
150
150
0
0
0
0
9
9
230
230
6
6
150
150