Fire Hazard - Carrier 25HBC5 Installation Instructions Manual

Single stage heat pumps with puron refrigerant 1–1/2 to 5 nominal tons
Hide thumbs Also See for 25HBC5:
Table of Contents

Advertisement

VALVE CORE
Fig. 5 – Vapor Service Valve
Brazing Connections
Connect vapor tube to fitting on outdoor unit vapor service valves
(see Table 2). Connect liquid tubing to adapter tube on liquid
service valve. Use refrigerant grade tubing.
CAUTION
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
Service valves must be wrapped in a heat–sinking material
such as a wet cloth while brazing.
Apply heat absorbing paste or heat sink product between service
valve and joint. Wrap service valves with a heat sinking material
such as a wet cloth.
After wrapping service valve with a wet cloth, tubing set can be
brazed to service valve using either silver bearing or non–silver
bearing brazing material. Do not use soft solder (materials which
melt below 800°F/427°C). Consult local code requirements.
NOTE: Some outdoor units contain a mechanical fitting at the
liquid distributor. This connection is not field serviceable and
should not be disturbed.
NOTE: For Liquid Service Valve − Braze lineset to adapter tube
BEFORE bolting adapter to valve. This helps prevent overheating
and damage to plastic washer or o−ring.
For Vapor Service Valve − remove valve core from schrader port
on Service Valve BEFORE brazing.
overheating and damage to valve seals (refer to Fig. 5). Replace
valve core when brazing is completed.
WARNING
!

FIRE HAZARD

Failure to following this warning could result in personal
injury, death and/or property damage.
Refrigerant and oil mixture could ignite and burn as it escapes
and contacts brazing torch. Make sure the refrigerant charge is
properly removed from both the high and low sides of the
system before brazing any component or lines.
Clean line set tube ends with emery cloth or steel brush. Remove
any grit or debris.
Insert line set tube ends into service valve tube stubs.
Apply heat absorbing paste or heat sink product between service
valve and joint. Wrap service valves with a heat sinking material
such as a wet cloth.
Braze joints using a Sil−Fos or Phos−copper alloy.
Table 2 – Refrigerant Connections and Recommended Liquid
UNIT SIZE
SERVICE VALVE
* Units are rated with 25 ft. (7.6 m) of lineset. See Product Data sheet for performance
Notes:
1. Do not apply capillary tube indoor coils to these units.
2. For Tubing Set lengths between 80 and 200 ft. (24.38 and 60.96 m) horizontal or
A14236
Installing with Indoor Piston
Heat pumps with piston indoor ratings are shipped with the correct
piston size in the accessory bag. Check piston size shipped with
indoor unit to see if it matches required indoor piston size. If it
does not match, replace indoor piston with correct piston size
which is listed on the rating plate.
NOTE:
installed as a replacement component in a piston system. When
installing a non−piston rated heat pump with with a piston indoor
the correct indoor piston must be installed. When not listed on the
rating plate the correct piston size is listed in the product data.
Replacement pistons can be ordered from Replacement
Components.
This helps prevent
Install Liquid Line Filter Drier Indoor
Refer to Fig. 7 and install filter drier as follows:
IMPORTANT: Installation of the filter drier in liquid line is
required.
4
and Vapor Tube Diameters (In.)
LIQUID
Connection
Tube
Diameter
Diameter
3/8
3/8
18, 24
3/8
3/8
30, 36
3/8
3/8
42, 48
3/8
3/8
60
data when using different size and length linesets.
20 ft. (6.09 m) vertical differential 250 ft. (76.2 m) Total Equivalent Length, refer to
the Residential Piping and Longline Guideline – Air Conditioners and Heat Pumps
using Puron refrigerant.
Heat pumps without piston indoor ratings may be
13/16" BRASS HEX NUT
TEFLON® SEAL
TEFLON®
RINGS
PISTON
PISTON RETAINER
Fig. 6 – Indoor Piston Installation
1. Braze 5 in. (127 mm) liquid tube to the indoor coil.
2. Wrap filter drier with damp cloth.
3. Braze filter drier to 5 in. (127 mm) long liquid tube from
step 1.
4. Connect and braze liquid refrigerant tube to the filter drier.
Fig. 7 – Liquid Line Filter Drier
RATED VAPOR
Connection
Tube
Diameter
Diameter
5/8
5/8
3/4
3/4
7/8
7/8
7/8
1–1/8
3/4" BRASS HEX BODY
"H" DISTRIBUTOR
A10342
A05227