6.39 Address 53 - History Controls
History Controls determine what events are stored in
the panels history buffer.
6.40 Address 54 - Custom Arming
Custom Arming programming allows the [#] + [4]
key sequence on the keypad to be used for custom
arming. The programming determines which zones
will be bypassed (not armed) during custom arming.
Note: Custom Arming will send a Partial Closed
report if programmed to do so in Address 31.
6.41 Address 55 - Zone Doubling
DS7060-AUS Reference Guide
Copyright © 2001 Detection Systems, Inc.
Zone Doubling adds three additional specific zones
to the control panel:
Zone 7 - Fire: Supervised for use with 4-wire smoke
detectors.
Zone 8 - Tamper: Supervised for use with tamper
switches.
Zone 9 - Keyswitch: Supervised keyswitch input. A
momentary contact closure on this input will toggle
the panel between the armed and disarmed states.
NOTE: The zone input wiring and End-Of-Line
resistors differ if Zone Doubling is selected. Be
sure to review Section 4.0, Terminal Wiring, for
the correct resistor selections.
6.42 Address 56 - Expanded Zone Reports
Expanded Zone Reports are used only if Zone
Doubling (see Address 55) is selected.
6.43 Address 57 - Expanded Zone Restorals
Expanded Zone Restorals are used only if Zone
Doubling (see Address 55) is selected.