6.8 Address 08 - Outputs
• Intrusion: This is an output programmed to latch with
any Burg zone alarm, including invisible and silent
zones. It will remain latched until the system is
disarmed regardless of the restore setting for the zone.
• On During Entry Pre-Alert: This is an output
programmed to activate when a perimeter delayed type
zone is violated while the system is armed. It will
remain activated until the system is disarmed, or until
the entry delay time has expired.
• System Reset: This is an output programmed to
activate only for 10 seconds after a PIN + [System
Reset] is entered at a keypad or if a fire zone with
verification activates. Output 1 turns on for 10 seconds,
outputs 2 and 3 turn off for 10 seconds. Outputs 2 and
3 are intended to be used to power 4-wire smoke
detectors or any other device that requires a power
interruption to reset an alarm condition.
• Armed: This is an output programmed to activate
when the system is armed. It will remain activated until
the system is disarmed.
• Ground Start: This is an output programmed to
activate for 3 seconds when the phone line is seized. It
is intended for use with ground start phone systems that
require a momentary short to ground to obtain a dial
tone. Connect a separate 12 VDC, DPDT relay.
Connect both relay commons to ground, and connect
the N/O of each contact to terminal positions 23 and 26
(one to terminal 23, one to 26) of the DS7060. Connect
one side of the relay coil to the selected Programmable
Output and the other side of the coil to 12 volts
Page 10
Copyright © 2001 Detection Systems, Inc.
(Terminal 5) (if PO1 or PO2 is used), or to any Panel
Common terminal if PO3 is used. Not intended for UL
Listed systems. Not for use with phone line monitors.
• Ready to Arm (System Status): This is an output
programmed to follow the "Status" light of the keypad. It
will activate when the system is ready to arm with no
zones violated.
• Follow Burg Alarm: This is an output programmed to
activate when a zone is in an alarm condition. It will
remain activated until the system is disarmed or the bell
cutoff time expires. This output is intended to activate
bells and sirens. This will not activate from Silent or
Invisible zones.
• Follow Fire Alarm: This is an output programmed to
activate when a zone is in an fire alarm condition. It will
remain activated until the system is disarmed (or
silenced using PIN + [Off] ) or the bell cutoff time
expires. This output is intended to activate bells and
sirens. This will not activate from Silent or Invisible
zones.
• Follow Burg and Fire Alarm: This programs an
output to activate when any zone goes into alarm
condition.
• Follow Keypad Sounder: This is an output
programmed to follow the keypad sounder. It activates
during the entry pre-alert . It does not follow momentary
keypad beeps such as keystrokes.
• Duress: This output activates when the duress code is
used to disarm the system.
NOTE: If the Duress code is used to activate a
Programmable Output, entering any valid PIN + [OFF}
will deactivate the Programmable Output.
• Trouble: This output activates when a trouble
condition is present.
• Off During Battery Test: This output turns Off
(deactivates) for 2 seconds during a manual or
automatic battery test.
• Partial Armed: This output activates whenever the
system is armed with one or more zones bypassed.
This includes manual bypasses, custom arming and
force arming.
• Follow Burg Alarm 20 Second Delay: This output will
be delayed for 20 seconds after a zone enters an alarm
condition. It will remain activated until the system is
disarmed or the bell timeout expires.
DS7060-AUS Reference Guide