Frequency Setting By External Terminals; Multi-Speed Setting Operation (Pr. 4 To Pr. 6, Pr. 24 To Pr. 27, Pr. 232 To Pr. 239) - Mitsubishi FR-A740-00023-EC Instruction Manual

Fr-a700 series
Table of Contents

Advertisement

Frequency setting by external terminals

4.11 Frequency setting by external terminals

Purpose
Make frequency setting by
combination of terminals
Perform jog operation
Added compensation for multi-speed
setting and remote setting
Infinitely variable speed setting by
terminals

4.11.1 Multi-speed setting operation (Pr. 4 to Pr. 6, Pr. 24 to Pr. 27, Pr. 232 to Pr. 239)

Can be used to change the preset speed in the parameter with the contact terminals.
Any speed can be selected by merely turning on-off the contact signals (RH, RM, RL, REX signals).
Parameter
Number
Multi-speed setting (high
4
speed)
Multi-speed setting (middle
5
speed)
Multi-speed setting (low
6
speed)
24
Multi-speed setting (speed 4)
25
Multi-speed setting (speed 5)
26
Multi-speed setting (speed 6)
27
Multi-speed setting (speed 7)
232
Multi-speed setting (speed 8)
233
Multi-speed setting (speed 9)
234
Multi-speed setting (speed 10)
235
Multi-speed setting (speed 11)
236
Multi-speed setting (speed 12)
237
Multi-speed setting (speed 13)
238
Multi-speed setting (speed 14)
239
Multi-speed setting (speed 15)
The above parameters allow its setting to be changed during operation in any operation mode even if "0" (initial value) is set in Pr. 77 Parameter write
selection.
Speed 1
(High speed)
Speed 2
(Middle speed)
Speed 4
Speed 3
(Low speed)
ON
RH
ON
ON
RM
ON
RL
Speed 10
Speed 11
Speed 12
Speed 9
Speed 13
Speed 8
ON ON ON ON
RH
ON ON
RM
ON
ON
ON
RL
ON
ON
ON ON ON ON ON ON
REX
*
160
Multi-speed operation
Jog operation
Multi-speed input
compensation selection
Remote setting function
Name
Initial Value
(1) Multi-speed setting (Pr. 4 to Pr. 6)
⋅ Operation is performed at the frequency set in Pr. 4 when the RH
Speed 5
Speed 6
signal turns on, Pr. 5 when the RM signal turns on, and Pr. 6 when the
RL signal turns on.
Speed 7
⋅ In the initial setting, if two or three speeds are simultaneously
Time
ON
ON
ON
ON
ON
ON
ON
⋅ The RH, RM, RL signals are assigned to the terminal RH, RM, RL in
Speed 14
Speed 15
(2) Multi-speed setting higher than speed 4 (Pr. 24 to Pr. 27,
Time
Pr. 232 to Pr. 239)
ON ON
⋅ Frequency from speed 4 to speed 15 can be set according to the
ON
combination of the RH, RM, RL and REX signals. Set the running
frequencies in Pr. 24 to Pr. 27, Pr. 232 to Pr. 239. (In the initial value
setting, speed 4 to speed 15 are unavailable.).
⋅ For the terminal used for REX signal input, set "8" in any of Pr. 178 to
Pr. 189 (input terminal function selection) to assign the function.
* When
frequency set in Pr. 6 when RH, RM and RL are turned off and REX is turned on.
Parameter that must be Set
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
Setting Range
50Hz
0 to 400Hz
30Hz
0 to 400Hz
10Hz
0 to 400Hz
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
REMARKS
selected, priority is given to the set frequency of the lower signal. For
example, when the RH and RM signals turn on, the RM signal (Pr. 5)
has a higher priority.
the initial setting.
By setting "0 (RL)", "1 (RM)", "2 (RH)" in any of Pr.178 to Pr.189 (input
terminal function assignment), the signals can be assigned to other
terminals.
"
"
9999
is set in Pr. 232 Multi-speed setting (speed 8), operation is performed at
Pr. 15, Pr. 16
Pr. 28
Pr. 59
Description
Set the frequency when RH turns on.
Set the frequency when RM turns on.
Set the frequency when RL turns on.
Frequency from speed 4 to speed 15
can be set according to the
combination of the RH, RM, RL and
REX signals.
9999: not selected
Refer to Page
160
162
164
164