Mitsubishi Electric 700 Series Programming Manual page 20

700 series plc function programming manual
Hide thumbs Also See for 700 Series:
Table of Contents

Advertisement

Number
Name
Output frequency
D9133
monitor
Output current
D9134
monitor
Output voltage
D9135
monitor
D9136
Error history 1, 2
D9137
Error history 3, 4
D9138
Error history 5, 6
D9139
Error history 7, 8
Operation mode
D9140
setting read
Set frequency
D9141
read (RAM)
Set frequency
D9142
2
read (E
PROM)
Operation mode
D9143
setting write
Set frequency
D9144
write (RAM)
Set frequency
D9145
2
write (E
PROM)
Alarm definition
D9146
batch clear
D9147
Parameter clear
Description
Stores the current output frequency.
0.01Hz units
Stores the current output current.
0.01A units
Stores the current output voltage.
0.1V units
Store the errors that occurred in the inverter in order
of occurrence.
Stores the current operation mode.
Reads and stores the set frequency (RAM).
Reads and stores the set frequency (EEPROM).
Sets a new operation mode.
Sets the running frequency (RAM).
Sets the running frequency (EEPROM).
Write H9696 to clear the error history.
H9696 write: Parameter clear
H9966 write: All clear
H5A5A write:Parameter clear except communication
parameters
H55AA write:All clear except communication
parameters
During GX Developer communication, perform
clearing by H5A5A or H55AA.
Device Map
Page
20
21
23
24
24
26
27
28
29
30
1
15