3.25.7 Output Instructions : Leading edge, trailing edge
differential outputs ... PLS, PLF
Bit devices
X
Y
D
PLS command
PLF command
Functions
PLS
(1) Turns the specified device on when the PLS command turns from OFF to ON,
and turns it off except when the PLS command turns from OFF to ON.
When there is one PLS instruction for the device specified at
the specified device turns on for one scan.
Do not execute the PLS instruction for the same device more than once during
one scan.
(2) If the status is switched to STOP and switched to RUN again after execution of
the PLS instruction, the PLS instruction is not executed.
Usable Devices
Word (16-bit) devices
M
T
C
D
Sequence Instructions
Constants
Level
Designation
K
H
N
Set data
Device number whose data
D
will be converted into pulses
1 scan
Error
Flag
Digit
(M9010,
M9011)
D
during one scan,
1 scan
129
3