Advertisement

5 - 5 Interlocked operation setting

• Registration of interlocked operation of Ventilation unit (OA processing unit and LOSSNAY) with single or multiple
indoor unit is performed. All indoor units to be interlocked with ventilation unit for operation should be registered
for the interlocking with ventilation unit.
<Example for the interlocked group configuration>
NEXT
1
Simultaneously press the
screen for 2 seconds.
NOTE:
Always perform the mode change operation from the user oper-
ation menu.
Mode change operation from other screens is ineffective even if
performed.
2
Initial setting menu screen is displayed.
3
Press the
switch to select "2 INTERLOCKED SETTING" .
2
4
The interlocked setting screen is displayed.
Minimum address of the interlocked OA processing unit or LOSSNAY unit
which can be set to interlock with indoor unit is displayed on the "INTERL-
OCKED UNIT ADDRESS" display position. And the cursor is displayed in
the unit address display position.
5
Press the
GROUP
SELECT
terlocked OA processor unit or LOSSNAY that the setting will be perf-
omed on.
-29-
Outdoor unit
Indoor unit
M-NET local remote controller
OA processing unit or LOSSNAY
M-NET
Transmission line
and
keys on the user operation menu
switch to display the address number of the in-