Initial Setting; Shifting To Initial Setting Menu; M-Net Address Setting - Mitsubishi Electric G-50A Instruction Book

Air-conditioner network system central controller
Hide thumbs Also See for G-50A:
Table of Contents

Advertisement

5

. Initial setting

5 - 1 Shifting to initial setting menu

• Shift to the initial setting menu by continuously pressing
screen.(Refer to section "3-2".)
Shift to the user operation menu by continuously pressing
(Refer to section "3-2".)
• When group information is not saved, the following initial setting screen is displayed when power is turned on at this
controller.

5 - 2 M-NET address setting

(1) Select
"6.ADDRESS SETTING"(or
6
(2) Set the controller address by pressing the
(3) When the
BACK
switch is pressed after setting, the screen returns.
SCREEN
MENU
6 ADDRESS SETTING
7 FUNCTION SETTING
8 IP ADDRESS SETTING
BACK
• When the controller is shipped from the factory, the address is set to "000".
(Always set the address to "000" When the K transmission converter is managed.)
Observe the following precautions when this controller manages the M-NET models and K control mod-
NOTE :
els by using the K transmission converter (PAC-SC25KAA).
Refer to the K transmission converter instruction manual for further details.
• Address of this controller
Always set the address of this controller to "000" .
• Function select setting of this controller
Always set the No.3 function setting to ON.
• Indoor unit address
Set all the M-NET models of indoor units from 001, next, set the address of the K control indoor unit.
Indoor unit address
* The K transmission converter (PAC-SC25KAA) is not included in systems shipped to North America
(USA & Canada).
1
0
Press the
WED 15:29
to select"6ADDRESS
SETTING"
Press the
switch to back
to the initial
setting menu.
001
M-NET indoor unit maximum address
mum address
+
(2seconds or longer) on the user operation menu
+
(2seconds or longer) on the initial setting screen
MENU
1 ADDRESS SETTING
2 FUNCTION SELECT
3 IP ADDRESS SETTING
4 GROUP SETTING
PLEASE SET
INITIAL SETTING
"1.ADDRESS SETTING).
to
switches.(000,201
9
INS.
switch
6
M-NET ADDRESS
M-NET ADDRESS:
BACK
SCREEN
050
-25-
WED 15:29
250).
000
K control indoor unit mini-