Mitsubishi Electric G-50A Instruction Book page 23

Air-conditioner network system central controller
Hide thumbs Also See for G-50A:
Table of Contents

Advertisement

(2) Set-back values and setting temperature setting
• Setting the set-back values and setting temperature can be performed only when selecting either "SET BACK"
or "SET TEMP" on the user setting screen in the initial setting mode.
• Set-back operation
Set-back operation is a method which reduces the air conditioner running cost by controlling the operation with
specified time band for lowered load. In other words the unit operates at a few degrees higher for cooling and
a few degrees lower for heating in the specified time band.
EXAMPLE
When the reference temperature is 24˚C / 75˚F and the set-back value is set to 2˚C / 4˚F.
• Cooling operation : 24˚C+2˚C=26˚C / 75˚F+4˚F=79˚F
• Heating operation : 24˚C-2˚C=22˚C / 75˚F-4˚F=71˚F
• Setting temperature operation
This operation sets the temperature when timer ON is set to a predesignated temperature regardless of the op-
eration mode.
* The selecting range:
• The reference temperature for set-back operation
• The set-back value
• The setting temperature
(3) Weekly schedule setting
The schedule pattern P1 to P3, local remote control prohibition (P4),
P1 to P3 and P4, and non-timer operation(-) are set for each day.
: 19˚C 28˚C (1˚C unit) / 67˚F 83˚F (2˚F unit)
: 0 9 degree (1 degree unit)
/ 0 18 degree (2 degree unit)
: 19˚C 28˚C (1˚C unit) / 67˚F 83˚F (2˚F unit)
1
Press the
schedule setting.
2
Press the
tern position to be set.
-21-
1
NOTE: The temperature display
2
3
4
5
P1
to
P3
of a composite pattern composed of
GROUP
switch to display the group in desired weekly
SELECT
switch to move the cursor to the pat-
Press the
switch to move the cursor posi-
tion to the set-back reference
temperature or setting tempera-
ture.
can be switched between
Celsius (°C) or Fahrenheit
(°F) (page 34).
Press the
/
5
8
(CLOCK/PATTERN) switch to
select the following items.
• Set-back value;
The reference temperature and
set-back value for each ON time
period are selected.
• Setting temperature:
The setting temperature for
each ON time period is selected.
ENTER
Press the
switch to make
setting.
Repeat operations
and
2
set the set-back value or setting
temperature for each ON/OFF
schedule.
BACK
Press the
switch, when finis-
SCREEN
hed.
to
3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents