Main Burner Flame Check - International comfort products N9MP1 Installation Instructions Manual

90+ single stage, category iv, gas furnace
Hide thumbs Also See for N9MP1:
Table of Contents

Advertisement

WARNING
!
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in
personal injury, death and/or property damage.
If any sparks, odors or unusual noises occur,
immediately shut OFF power to furnace. Check for
wiring errors or obstruction to blower.
Manifold Gas Pressure Adjustment
NOTE: Make adjustment to manifold pressure with burners
operating.
1.
Remove the burner compartment door.
2.
Remove the blower compartment door. Place a jumper
across furnace controls R to W. Replace blower
compartment door.
3.
With gas OFF, connect manometer to tapped opening on
gas valve. Use manometer with a 0 to 15 inch water column
range.
4.
Turn gas ON and remove adjustment screw cover on gas
valve. Turn adjusting screw counterclockwise to decrease
manifold pressure and clockwise to increase pressure.
Figure 45
Typical Gas Control Valve
Regulator Adjustment
Under Cap
INLET
Inlet
Pressure
1
Tap
/
NPT
8
NOTE: Adjustment screw cover MUST be replaced on gas control
valve before reading manifold pressure and operating furnace.
5.
Set manifold pressure to value as shown in Table 9,
Table 10, Table 11 or Table 12 under GAS SUPPLY AND
PIPING section in this manual.
6.
When the manifold pressure is properly set, replace the
adjustment screw cover on the gas control valve.
7.
Remove blower compartment door. Remove jumper wire
from thermostat connection on furnace control board.
Remove manometer connection from manifold pressure
tap, and replace plug in manifold.
8.
Check for leaks at plug.
9.
Replace the burner and blower compartment doors.
Natural Gas Input Rating Check
NOTE: The gas meter can be used to measure input to furnace.
Rating is based on a natural gas BTU content of 1,000 BTU's per
cubic foot. Check with gas supplier for actual BTU content.
1.
Turn OFF gas supply to all appliances and start furnace.
Use jumper wire on R to W for Heat.
2.
Time how many seconds it takes the smallest dial on the gas
meter to make one complete revolution. Refer to Example.
NOTE: If meter uses a 2 cubic foot dial, divide results
(seconds) by two.
440 01 1024 04
Natural Gas
BTU Content
To Determine the appliance kW input rate from a .05m
that has been clocked at 80 seconds for one complete revolution.
seconds per
3.
4.

Main Burner Flame Check

Allow the furnace to run approximately 10 minutes then inspect the
main burner. See Figure 46.
Check for the following (Figure 46):
Outlet
Pressure
Tap
1
/
NPT
8
If any problems with main burner flames are noted, it may be
OUTLET
necessary to adjust gas pressures, or check for drafts.
Figure 46
NOTE: For Ignitor location see Figure 47.
NOTE: Flame sensor has a different orientation in all 050 models.
Specifications are subject to change without notice
Example (BTUH)
No. of
Seconds
Per Hour
1,000
3,600
1,000 x 3,600 ÷ 48 = 75,000 BTUH
Example (kW)
Number of
Number of
seconds per
complete
hour
rotation
3,600
80
3,600 ÷ 80 x .05 = 7.2 m
3
2.25m
/h x 10.35 kWh/m
23.28 x 3.412 = 79,431 BTU
Remove jumper wire from R to W.
Relight all appliances and ensure all pilots are operating.
• Stable and blue flames. Dust may cause orange tips or
wisps of yellow, but flames MUST NOT have solid, yellow
tips.
• Flames extending directly from burner into heat
exchanger.
• Flames do NOT touch sides of heat exchanger
Main Burner
Burner Face
Figure 47
Ignitor Location
1/
2
(52.4)
16
5
/
(8)
16
Time Per
BTU Per
Cubic Foot in
Hour
Seconds
48
75,000
3
test dial
Size of test dial
3
kW m
/h
3
(.05m
)
.05
2.25
3
/h
3
= 23.28 kW
.
10−10−78
in(mm)
1
/
(6.4)
4
43

Advertisement

Table of Contents
loading

This manual is also suitable for:

N9mpdC9mpdH9mpdT9mpdN9mp2

Table of Contents