NATURAL GAS MANIFOLD PRESSURE (in wc)
Table 11
FOR THE 40k, 60k & 80k BTUH MODEL AND ALTERNATE INPUT MODELS
HEATING
0 to 2000
VALUE
(0 to 609.6)
at ALTITUDE
Orifice
Manifold
BTU/CU. FT.
No.
Pressure
700
−−
−−
725
−−
−−
750
−−
−−
775
−−
−−
800
−−
−−
825
−−
−−
850
−−
−−
875
−−
−−
900
−−
−−
925
44
3.7
950
44
3.5
975
44
3.3
1000
44
3.2
1050
46
3.6
1100
46
3.3
Conversion: 1 in wc = .25kPa
NOTE:
Natural gas data is based on 0.60 specific gravity. For fuels with different specific gravity consult the National Fuel Gas Code ANSI Z223.1/NFPA
54−2009 or National Standard of Canada, Natural Gas And Propane Installation Code CSA B149.1−05.
*
In the USA, derating of these furnaces at 2% (Natural Gas) and 4% (Propane Gas) has been tested and design−certified by CSA.
In Canada, the input rating must be derated 5% (Natural Gas) and 10% (Propane Gas) for altitudes of 2,000 to 4,500 (609.6 to
1371.6m) above sea level. Use the 2001 to 3000 (609.9 to 914.4m) column in Table 9, Table 10, Table 11 and Table 12.
PROPANE GAS MANIFOLD PRESSURE (in wc)
Table 12
FOR THE 40k, 60k & 80k BTUH MODEL AND ALTERNATE INPUT MODELS
HEATING VALUE
at ALTITUDE
0 to 2000
BTU/CU. FT.
(0 to 609.6)
2500
10.0
Orifice Size
#55
Conversion: 1 in wc = .25 kPa
NOTE:
Propane data is based on 1.53 specific gravity. For fuels with different specific gravity consult the National Fuel Gas Code ANSI Z223.1/NFPA
54−2009 or National Standard Of Canada, Natural Gas And Propane Installation Code CSA B149.1−05.
*
In the USA, derating of these furnaces at 2% (Natural Gas) and 4% (Propane Gas) has been tested and design−certified by CSA.
In Canada, the input rating must be derated 5% (Natural Gas) and 10% (Propane Gas) for altitudes of 2,000 to 4,500 (609.6 to
1371.6m) above sea level. Use the 2001 to 3000 (609.9 to 914.4m) column in Table 9, Table 10, Table 11 and Table 12.
The burner orifice part nos. are as follows:
Orifice
Part #
41
1096942
43
1011377
45
1011353
47
1011378
49
1113202
55
1011354
General Derating Rules
1.
These furnaces may be used at full input rating when
installed at altitudes up to 2,000' (609.6m). When installed
above 2,000' (609.6m), the input must be decreased 2%
(natural) or 4% (Propane) for each 1000' (304.8m) above
sea level in the USA. In Canada, the input rating must be
derated 5% (natural) or 10% (Propane) for each 1000'
(304.8m) above sea level. See Table 11 or Table 12 for
required high altitude input rate.
36
MEAN ELEVATION ABOVE SEA LEVEL − ft(m)
2001 to 3000*
3001 to 4000
(609.9 to 914.4)*
(914.7 to 1219.2)
Orifice
Manifold
Orifice
Manifold
No.
Pressure
No.
Pressure
−−
−−
−−
−−
−−
−−
−−
−−
−−
−−
−−
−−
−−
−−
−−
−−
−−
−−
−−
−−
−−
−−
43
3.7
−−
−−
43
3.5
43
3.4
43
3.3
44
3.7
44
3.6
44
3.5
44
3.4
44
3.3
44
3.2
44
3.1
45
3.7
45
3.6
45
3.5
45
3.3
45
3.2
45
3.0
46
3.0
MEAN ELEVATION ABOVE SEA LEVEL − ft(m)
2001 to 3000*
3001 to 4000
(609.9 to 914.4)*
(914.7 to 1219.2)
8.9
8.4
#55
#55
Orifice
Part #
42
1011351
44
1011352
46
1011744
48
1113201
54
1011376
56
1011355
Specifications are subject to change without notice
4001 to 5000
5001 to 6000
(1219.5 to 1524)
(1524.3 to 1828.8)
Orifice
Manifold
Orifice
Manifold
No.
Pressure
No.
Pressure
−−
−−
−−
−−
−−
−−
−−
−−
−−
−−
−−
−−
−−
−−
41
2.9
42
3.1
43
3.6
43
3.6
43
3.4
43
3.4
44
3.7
44
3.6
44
3.5
44
3.4
44
3.3
44
3.2
44
3.1
44
3.1
45
3.6
45
3.5
45
3.4
45
3.4
45
3.2
45
3.1
46
3.1
46
2.9
−−
−−
4001 to 5000
5001 to 6000
(1219.5 to 1524)
(1524.3 to 1828.8)
10.0
10.0
#56
#56
2.
For operation with natural gas at altitudes above 2,000'
(609.6m), orifice change and/or manifold pressure
adjustments may be required for the gas supplied. First
consult your local gas supplier, then refer to Table 9 for
required pressure change and/or orifice change for high
altitudes.
3.
For operation with Propane gas, gas orifices MUST be
changed and manifold pressure MUST be maintained as
per Table 10. Orifices can be ordered through our
distributor. (See Figure 33)
20,000 BTU per burner
6001 to 7000
7001 to 8000
(1829.1 to 2133.6)
(2133.9 to 2438.4)
Orifice
Manifold
Orifice
Manifold
No.
Pressure
No.
Pressure
−−
−−
42
3.6
42
3.5
42
3.4
42
3.3
42
3.2
43
3.7
43
3.6
43
3.5
43
3.4
43
3.3
44
3.6
44
3.6
44
3.4
44
3.4
44
3.2
44
3.2
44
3.1
45
3.6
45
3.5
45
3.5
45
3.3
45
3.3
45
3.2
45
3.1
46
3.1
−−
−−
−−
−−
−−
−−
−−
−−
20,000 BTU per burner
6001 to 7000
7001 to 8000
(1829.1 to 2133.6)
(2133.9 to 2438.4)
10.0
10.0
#56
#56
440 01 1024 04