International comfort products N9MP1 Installation Instructions Manual page 18

90+ single stage, category iv, gas furnace
Hide thumbs Also See for N9MP1:
Table of Contents

Advertisement

Condensate Drain Trap
This furnace removes both sensible and latent heat from the
products of combustion. Removal of the latent heat results in
condensation of the water vapor. The condensate is removed from
the furnace through the drains in the plastic transition and the vent
fitting. The drains connect to the externally mounted condensate
drain trap on the left or right side of the furnace.
The startup of a new furnace will involve a cycle or two of the
furnace to properly prime the condensate trap with water. Until the
trap is fully primed, some condensate will be pulled into the
combustion blower. The furnace may cycle on the pressure switch
connected to the plastic transition box due to condensate buildup.
After the trap is primed, the condensate will start draining from the
furnace. The combustion blower will clear out any remaining
condensate in the blower housing through the vent fitting
downstream of the blower. Note that the condensate trap can also
be primed by pouring water into the
1
Remove the
/
" (12.7mm) ID drain hose from either the gutter or
2
the white PVC tee trap. Using a funnel pour eight (8) ounces (236
1
ml) of water into
/
" (12.7mm) ID drain hose. Water will flow
2
through the drain hose and into the condensate drain trap. This will
prime both the vent and the transition sides of the trap. Reconnect
1
the
/
" (12.7mm) ID drain hose to the original component, either
2
the gutter or the PVC tee trap.
The condensate drain trap supplied with the furnace MUST be
used. The drain connection on the condensate drain trap is sized
3
for
/
" (19.1mm) PVC or CPVC pipe, however alternate
4
5
(12.7mm) CPVC [nominal
/
8
a minimum inner diameter (I.D.) of
used, as allowed by local codes. Alternate drain pipes and hoses
may be used as allowed by local codes.
The drain line must maintain a
1
slope toward the drain.
/
" (6.4mm) per foot is recommended.
4
Installation of an overflow line is recommended when the
(6.4mm) per foot slope to the condensate drain cannot be
maintained. A drain tube retainer clip is included in the furnace to
prevent kinking/buckling of the drain tube. The retainer clip should
remain in the furnace (between the door switch plate and the
blower shelf, Figure 10) during operation. See Figure 20 for
proper routing and installation of the overflow.
Figure 10
Drain Tube Retainer Clip Location
Drain
Tube
Clip
Blowe
Door
r Shelf
Switch
Representative drawing only, some models may vary in appearance.
18
1
/
" (12.7mm) drain hose.
2
" (15.9mm) O.D.] or vinyl tubing with
5
/
" (15.9mm) may also be
8
1
/
" (6.4mm) per foot downward
4
Specifications are subject to change without notice
DO NOT trap the drain line in any other location than at the
condensate drain trap supplied with the furnace.
!
FROZEN AND BURST WATER PIPE HAZARD
Failure to follow this caution may result in property
damage.
If a condensate pump is installed, a plugged
condensate drain or a failed pump may cause the
furnace to shut down. Do not leave the home
unattended during freezing weather without turning
off water supply and draining water pipes or
otherwise protecting against the risk of frozen pipes.
If possible, DO NOT route the drain line where it may freeze. The
drain line must terminate at an inside drain to prevent freezing of
the condensate and possible property damage.
1.
A condensate sump pump MUST be used if required by
local codes, or if no indoor floor drain is available. The
condensate pump must be approved for use with acidic
condensate.
2.
A plugged condensate drain line or a failed condensate
pump will allow condensate to spill. If the furnace is installed
where a condensate spill could cause damage, it is
recommended that an auxiliary safety switch be installed to
1
/
"
prevent operation of the equipment in the event of pump
2
failure or plugged drain line. If used, an auxiliary safety
switch should be installed in the R circuit (low voltage)
ONLY.
3.
If the auxiliary switch in the condensate pump is used, the
furnace may shut down due to a blocked condensate line or
failed pump. To prevent frozen water pipes see the "Frozen
1
/
Water Pipe Hazard" section in this manual.
"
4
Condensate Drain Trap Freeze Protection
Special precautions MUST be made if installing furnace in an area
which may drop below freezing. This can cause improper
operation or damage to the equipment. If the the furnace
environment has the potential of freezing, the drain trap and drain
line must be protected. Use 3 to 6 watt per foot at 115 volt, 40° F
(4°C) self−regulating shielded and waterproof heat tape. Wrap the
drain trap and drain line with the heat tape and secure with the ties.
Follow the heat tape manufacturer's recommendations.
CAUTION
440 01 1024 04

Advertisement

Table of Contents
loading

This manual is also suitable for:

N9mpdC9mpdH9mpdT9mpdN9mp2

Table of Contents