Rinnai 37AHA04508KA5 Installation, Operation And Maintenance Manual page 29

37aha series hydronic air handler
Hide thumbs Also See for 37AHA04508KA5:
Table of Contents

Advertisement

Table 3: Hydronic Air Handler Specifications
UNIT MODELS
Trade Name
RATING AND PERFORMANCE
Nominal Output Capacity (BTU/h) †
Air Side Temperature Rise Rate in
( 68ºF Entering Air @ 150ºF Entering Water)
External Static Pressure
Nominal Airflow (CFM)
ELECTRICAL
Power Supply
Minimum Circuit Ampacity
Max. Rating of Overcurrent Protective Device
Maximum Fuse or CKT BKR Size
Transformer (24V)
Printed Circuit Board
CONTROLS
Available Unit Configurations
Safety Door Switch
Blower Off Delay
Cool / Heat Blower On Delay
INDOOR BLOWER MOTOR
Type
Motor HP
Motor (Rated Load Amps/Locked Rotor Amps)
Run Capacitor
Volts-PH-HZ
CIRCULATING PUMP
Type
Volts-PH-HZ
Motor (Full Load Amps/Locked Rotor Amps)
Pump Motor HP
Run Capacitor
Maximum Working Pressure
Min/Max Fluid Temperature
HYDRONIC HEATING COIL
Coil Construction
Rows...Fins/In
Total Face Area
Approximate Internal Volume
PIPING CONNECTIONS - (QTY)
Type
Supply Diameter
Return Diameter
RETURN-AIR FILTERS
Filter Type (Throwaway)
UNIT WEIGHT
Shipping
Installed (with water)
Rinnai is continually updating and improving products. Therefore, specifications are subject to change without prior notice.
Tested in accordance with ANSI/ASHRAE Standard 37-1988
Airflow shown is for bottom only return-air (blower speed factory set). For
air delivery other than stated, refer to Dry Coil Air Delivery table.
†† Required filter sizes shown are based on the larger of the ARI (Air
Conditioning & Refrigeration Institute) rated cooling airflow or the heating
airflow velocity of 300 ft/min for throwaway type or 450 ft/min for high-
capacity type.
37AHA04508KA5 37AHA06012KA5 37AHA07514KA5 37AHA09016KA5
Descriptor (Typ.)
o
F
Heat Speed
(in. W.C.)
Heating
Cooling Range
V - HZ - PH
MCA
MOP (Calculated)
Amps
PCB
A/C or HP
Single or Two Stage
FS or WH
Rated Voltage
Resistive Load
HTG/CLG
Varies
RLA/LRA
mfd/volts
FLA/LRA
mfd/volts
PSI
ºF (ºC)
Sq. Ft.
Gallons
Inches
Inches
Inches ††
lbs
lbs
Rinnai Corporation Hydronic Air Handler Manual
AH45
AH60
45,000
60,000
50
50
0.5
0.5
800 ‡
1200 ‡
650 - 800
650 - 1200
6.3
8.7
9.9
14.2
15
15
40 VA (Primary: 120 VAC / Secondary: 24 VAC)
INTEGRAL (with connections for A/C system, UV lamp, Humidifier, and
electronic air cleaner)
Dip Switch Selectable (SW1)
Dip Switch Selectable (SW1)
Shunt Selectable (P-7)
Dip-switch Selectable/Fixed 30 Sec
Cool: 1 second / Heat: 25 seconds (see Sequence of Operations)
DIRECT DRIVE MOTOR (PSC)
1/3
1/2
3.6 / 11.0
5.5 / 18.2
10/370
120 (49) / 160 (71)
3/8" OD copper tubes, aluminum fins, galvanized steel frame
2...16
2...16
2.3
2.6
0.47
0.53
Copper Stubs
12 X 20 X 1
16 X 20 X 1
92
109
107
127
Side intake filter to be (1) 20"x20"x1" typical for all models.
Air filter pressure drop for non-standard filters must not exceed 0.08 in. wg.
AH75
75,000
50
0.5
1400 ‡
1000 - 1600
1200 - 1750
115-60-1
13.7
23.2
20
125 VAC
21 Amp
3/4
9.5 / 21.5
10.0 / 22.2
115-1-60
Wet Rotor
115-1-60
1.8 / 2.6
1/8
14/250
125
3...14
2.8
0.86
(1) 3/4
(1) 3/4
20 X 20 X 1
(2) 12 X 20 X 1
118
138
AH90
90,000
50
0.5
1600 ‡
14.3
24.3
20
1
25/370
3...15
3.3
1.02
136
159
29