Installation
Attachment Methods Using Straps
Method 1
Use (4) #8 x 3/4 sheet metal screws for each strap.
The straps should be vertical against the Air Handler
sides and not pull away from the Air Handler sides.
Method 2
Fold all straps under the Air Handler and secure with
(4) #8 x 3/4 sheet metal screws (2 screws at the side
and 2 screws at the bottom. (Care must be taken not
to drive the screw through the coil.)
1 INCH x 22 GAUGE
GALVANIZED STRAPS
TYPICAL FOR 4 STRAPS
DOOR
ASSEMBLY
COIL
INTERFACE
AREA
SUPPLY AIR OPENING
Figure 7:
Horizontal Unit Suspension with Straps
DUCT CONNECTIONS
Supply Duct
The supply ductwork must be attached to the outside
of the flange on the air discharge end of unit. Flexible
connectors may be used if desired.
Return Duct
The return ductwork should be attached to the air
return side (bottom or side) of unit using sheet metal
screws or other fasteners.
For side return air inlet installation see the Figures 3
and 4.
FILTER INSTALLATION
Internal filter rack and a 1 inch disposable filter are
standard on all models. Refer to the Specifications
section for dimensions.
RETURN AIR
OPENING
BACK OF AHU
Rinnai Corporation Hydronic Air Handler Manual
AIR DISTRIBUTION SYSTEM
Existing Ductwork
It is the responsibility of the installer to inspect all
previously installed air distribution system to determine
its suitability for the new heating and/or cooling
system. Existing ductwork may have to be modified
and/or insulated to provide satisfactory air distribution.
Ductwork Installation
Connect the supply-air duct over the outside of 3/4-in.
flange on the unit's discharge side. Secure the duct to
the flange with proper fasteners for the type of duct
used. Support the duct independently.
Use flexible connectors (if desired between the
ductwork and the unit to prevent transmission of
vibration.
Use insulation with vapor barrier for ductwork passing
through unconditioned spaces.
PROHIBITED INSTALLATIONS
Front
The air inlet is not allowed to be at
Figure 8:
the front or back of the Air Handler
Do not position the Air Handler on
Figure 9:
its back or with it face down.
NOTE:
Multiple Air Handlers configured for installation with a
single Rinnai Tankless Water Heater is prohibited.
Back
9