Rinnai ES38 RHFE-1004RFA Conversion Manual

Rinnai es38 energysaver gas direct vent wall furnace
Hide thumbs Also See for ES38 RHFE-1004RFA:
Table of Contents

Advertisement

Available languages

Available languages

for the conversion from
Natural Gas (NG) to Liquid
Propane Gas (LPG)
for the conversion from
Liquid Propane Gas (LPG) to
Natural Gas (NG)
for adjustments at high altitude
(greater than 2000 ft / 610 m)
WARNING
This conversion kit shall be installed by a qualified service agency in
accordance with the manufacturer's instructions and all applicable codes and
requirements of the authority having jurisdiction. If the information in these
instructions is not followed exactly, a fire, explosion or production of carbon
monoxide may result causing property damage, personal injury or loss of life.
The qualified service agency is responsible for the proper installation of this
kit. The installation is not proper and complete until the operation of the
converted appliance is checked as specified in the manufacturer's instructions
supplied with the kit.
This is the safety alert symbol. This symbol alerts you to potential hazards that can kill or
hurt you and others.
DANGER
WARNING
CAUTION
Conversion Manual for the
ES38
(RHFE-1004RFA)
(RHFE-1004FTA)
Energysaver
Gas Direct Vent Wall Furnace

Safety Symbols

Indicates an imminently hazardous situation which, if not avoided, will result
in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, could result
in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, could result
in minor or moderate injury. It may also be used to alert against unsafe
practices.
®
English
Technical Data ......................... 2
Conversion Procedure ............. 3
Parts List ................................ 11
Français
Données Techniques ............... 7
Liste des Pièces ..................... 11

Advertisement

Table of Contents
loading

Summary of Contents for Rinnai ES38 RHFE-1004RFA

  • Page 1: Table Of Contents

    Conversion Manual for the ES38 (RHFE-1004RFA) (RHFE-1004FTA) Energysaver ® Gas Direct Vent Wall Furnace for the conversion from ⇒ English Natural Gas (NG) to Liquid Technical Data ......2 Propane Gas (LPG) High Altitude Installaton ... 2 Conversion Procedure ..... 3 for the conversion from ⇒...
  • Page 2: Technical Data

    For high altitude installations in Canada, the conversion shall be carried out by a manufacturer’s authorized representative, in accordance with the requirements of the manufacturer, provincial or territorial authorities having jurisdiction and in accordance with the requirements of CAN/CGA-B149.1 or CAN/CGA-B149 installation codes. Rinnai Corporation ES38 Conversion Manual...
  • Page 3: Conversion Procedure

    3 notches are showing - this is 70% air. procedure, Adjust Gas Pressure Settings. The air rods can be found directly under each gas line at the combustion chamber. Retighten set screw once adjustments have been made. Rinnai Corporation ES38 Conversion Manual...
  • Page 4 9. Compare the pressure reading on the manometer to the correct table for your gas type. If necessary adjust the low fire pressure using the ▲ and ▼ buttons. Press the Economy switch to record into Rinnai Corporation ES38 Conversion Manual...
  • Page 5 12. The LED will display two digits - a “7” and another number. If the LED shows any thing else call Rinnai Technical Support at 1-800-621-9419 for assistance. 13. Press the ON/OFF button again. The LED display turns blank and the appliance returns to the normal OFF mode.
  • Page 6 évitée peut entraîner des blessures graves voire mortelles. Indication d’une situation potentiellement dangereuse, qui si elle n’est pas évitée ATTENTION peut entraîner des blessures légères ou moyennes. On peur également l’utiliser pour signaler des pratiques non sûres. Rinnai Société ES38 Manuel de Conversion...
  • Page 7: Données Techniques

    Pour des installations d'altitude élevée au Canada, la conversion doit être effectuée en suivant les conditions requises par les autorités des provinces ayant jurisdiction et conformément aux exigences 1 et 2 du Code d’Installation CAN1-B149. Rinnai Société ES38 Manuel de Conversion...
  • Page 8: Procédure De Conversion

    Avant d’effectuer la conversion, couper d’abord l’alimentation en gaz, ensuite, couper ATTENTION l’alimentation électrique. Confirmer que la pression de gaz d'arrivée est entre les pressions de minimum et maximum a tenu le compte de cet appareil Rinnai Société ES38 Manuel de Conversion...
  • Page 9 étant utilisé. Si nécessaire ajuster la pression basse de feu utilisant le ▲ et ▼ boutons. Appuyer le Economy commutateur. Appuyez deux fois sur le commutateur SW1. 10. Le ÉCRAN affichera « PH ». Rinnai Société ES38 Manuel de Conversion...
  • Page 10 Appuyer le Economy commutateur. 12. L'affichage montrera à deux chiffres - un « 7 » et un autre numéro. Si l'affichage montre autre chose avec Rinnai pour assistance (1-800-621- 9419). 13. Appuyer l'interrupteur encore. Le vide ÉCRAN de virages d'exposition et l'appareil retournent au normal du mode.
  • Page 11: Parts List

    (High) 1004F-2031-B-1.80 NAT. Injecteur (haut) Injector (Low) 1004F-2036-B-1.95 NAT. Injecteur (bas) Injector (High) 1004F-2031-A-0.95 Injecteur (haut) Injector (Low) 1004F-2036-A-1.20 Injecteur (bas) Conversion Plate CP-72317-21 NAT. Plaque de conversion Conversion Plate CP-72317-22 Plaque de conversion Rinnai Société ES38 Manuel de Conversion...
  • Page 12 RHFE1004-0329(00) Printed in Japan 2011.04 © 2011 Rinnai America Corporation...

This manual is also suitable for:

Es38 rhfe-1004fta

Table of Contents